Section 9 • Step and PID Device Control Screens
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Aftercooler Screens
Figure 9-4. Aftercooler (VFD Type) Screen
AFTERCOOLER (VFD TYPE) SETPOINTS
Start Aftercooler Above: De nes the temperature the
aftercooler fans will come on at minimum speed.
Target Aftercooler Outlet Temperature: De nes the
desired temperature of gas at the outlet of the after-
cooler. The aftercooler fan speed will adjust to main-
tain this temperature.
Deadband: Range above and below setpoint where
the controller will not make adjustments to fan speed.
PID Tuning: PID Calculations displayed to aid in tun-
ing the PID loop.
Loop Update Time: De nes the PID controller loop
time. The PID calculation will update every cycle of
the loop update timer.
Proportional Gain (Kp): De nes the Proportional
Constant of the PID calculation.
Integral Gain (Ki): De nes the Integral Constant of
the PID calculation.
Derivative Gain (Kd): De nes the Derivative Constant
of the PID Calculation.
• Minimum Speed: De nes the minimum aftercooler
fan speed.
Aftercooler VFD Force: Allows the user to manu-
ally force the aftercooler fan(s) to a settable speed.
Activating the Aftercooler VFD Force pushbutton
will command the aftercooler fan(s) to go to the set
speed, and will override calculations from the PID
Controller