Section 10 • Diagnostic Screens
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
IO/Comms Diagnostics Screen
Figure 10-1. IO/Comms Diagnostics Screen
COMMS DIAGNOSTICS AND I/O STATUS
NOTE
Some screens may have inverted colors for ease of
readability.
The IO/Comms Diagnostics Screen is divided into 3
sections.
• SYSTEM INFORMATION
Shows basic information about the Compressor
PLC panel: Vilter sales order number, Software
revision, IP addresses, hardware information, and
rmware revisions of compressor PLC and HMI.
BITS/REALS FROM DCS:
Shows commands from a central controller or
DCS to verify communications setup with a cen-
tral controller or DCS.
LOCAL I/O STATUS
Shows a graphic representation of the compres-
sor PLC’s local I/O modules and the raw data spe-
ci c to each channel.
• Use the following rules to interpret the data:
• Discrete inputs and outputs: Green = ON
Analog Inputs (voltage): The number shown
for a speci c channel represents the voltage
signal being read in millivolts. Ex: a value of
2500 indicates 2500 millivolts or 2.5 volts.
Analog Inputs and outputs (4-20mA): The
number shown for a speci c channel rep-
resents the signal in .001 mA. Ex: a value of
4000 indicates 4.000 mA.
RTD Inputs: The number shown for a speci c
channel represents the temperature reading
in Fahrenheit times 10. Ex: a value of 730 in-
dicates 73.0 degrees Fahrenheit.