Section 12 • Communications with a Central Controller/DCS
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Compressor Commands: “REAL_IN” (Data Type = REAL)
Interface Tag Description Units
REAL_IN[0]
Remote Discharge Pressure Setpoint PSIA
REAL_IN[1]
Remote Process Temp Setpoint PSIA
REAL_IN[2]
Remote Suction Pressure Setpoint PSIA
REAL_IN[3]
Common Discharge Header Pressure From DCS PSIA
REAL_IN[4]
Common Suction Header Pressure From DCS PSIA
REAL_IN[5]
Capacity Slide Position Command From DCS % Position
Table 12-10. Compressor Command (Real)
DISCRETE COMPRESSOR COMMANDS
Discrete Compressor commands are presented in
Double Integer Format. To send discrete commands,
it is necessary to address the speci c bits of the Double
Integer.
Write Data: “BOOL_IN” (Data Type = DINT)
Interface Tag Description
BOOL_IN[1].0
Soft Capacity Decrease Command from DCS
BOOL_IN[1].1
Soft Capacity increase Command from DCS
BOOL_IN[1].2
Local Mode Command from DCS
BOOL_IN[1].3
Remote Mode Command from DCS
BOOL_IN[1].4
Reset Alarms from DCS
BOOL_IN[1].5
Soft Run Command from DCS
BOOL_IN[1].6
Command to Switch to Setpoint 1
BOOL_IN[1].7
Command to Switch to Setpoint 2
BOOL_IN[1].8
BOOL_IN[1].9
BOOL_IN[1].10
BOOL_IN[1].11
BOOL_IN[1].12
BOOL_IN[1].13
BOOL_IN[1].14
BOOL_IN[1].15
Table 12-11. Compressor Command (Double Integer)
If Control by communications is enabled from the
Con guration Screen, the soft run command (BOOL_
IN[1].5) must be held HIGH in addition to the remote
permissive physical input.