12 – 25
Section 12 • Communications with a Central Controller/DCS
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Compressor State and Mode Indicator
The state of the compressor state indicator shown on the compressor and system overview screens can be monitored.
State Indicator (Data Type = DINT, Length = 1)
Tag Description
COMP_STATE_IND Compressor State Indicator
State Description
0
Stopped
1
Standby
2
Moving Slides to Minimum Position
3
Pre-lube
4
Pre-lube - Compressor Starting
5
Compressor Warm-up
6
Running
Table 12-8. State Indicator
Mode Indicator (Data Type = DINT, Length = 1)
Tag Description
MODE_IND Compressor State Indicator
State Description
1
Local-Auto
2
Local-Manual
3
Remote-Auto
4
Remote-Manual
Table 12-9. Mode Indicator
Sending Commands to Compressor PLC (Ethernet IP Version)
To send commands to the Compressor PLC, Control by Communications must be enabled from the Con guration
screen and the watchdog must show that communications between the Compressor PLC and Central Controller/DCS
are not faulted. On a communication fault, the commands from the Central controller will stay in their last state/value
in the compressor PLC.
WATCHDOG BITS
NOTE
When PLC Sees BOOL_IN[0].0 OFF it will turn BOOL_OUT[0].0 ON. DCS Shall Turn BOOL_
IN[0].0 ON when it sees BOOL_OUT[0].0 ON to maintain the handshake.
TO DCS: BOOL_OUT[0].0
FROM: BOOL_IN[0].0