6 – 5
Section 6 • Instrument Calibration
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
The Other Analog Device Calibration Screen allows the
user to calibrate additional 4-20mA input devices.
4-20mA devices that can be calibrated:
Main Motor Amperage
Main Motor VFD Speed
Compressor and Motor Vibration Sensors
• Methane Detector
CALIBRATE AN ADDITIONAL INSTRUMENT
To calibrate an additional instrument, proceed with the
following steps.
1. Enter the raw mA range (typically 4-20mA).
2. Enter the Span of the transmitter.
3. Enter minimum scale value in “XDCR Min” and full
scale value for “XDCR Max.”
Other Analog Device Calibration
Figure 6-5. Other Analog Calibration Screen