Section 2 • Operational Descriptions
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
WATER COOLED GAS AFTERCOOLER
Reference Figure 2-13
If installed, the water-cooled gas aftercooler is a heat ex-
changer that uses a modulating valve to control cooling
water ow to remove heat from the gas discharged by
the compressor. The valve position is adjusted to control
the amount of cooling done by the aftercooler.
A PID controller adjusts the opening degree of the
modulating valve to maintain a desired temperature at
the outlet of the gas aftercooler. When the aftercooler
outlet temperature exceeds the desired pressure plus a
deadband, the valve will open further to add more cool-
ing. When aftercooler outlet temperature drops below
the desired temperature minus a deadband, the valve
will begin to close.
When the compressor is stopped, the valve will be
commanded to 0% open (full close).
When the compressor is running and the condensing
pressure rises above the “Open Valve At” setpoint in
the “Water Cooled Aftercooler Setpoints” screen, the
valve will open to a settable minimum position.
When the compressor is running and the aftercooler
outlet temperature is above the deadband, the PID
controller will increase the valve opening degree.
When the compressor is running and the aftercooler
outlet temperature is below the deadband, the PID
controller will decrease the valve opening degree.
Figure 2-13. Operational Diagram - Water Cooled Gas Aftercooler
TARGET
OUTPUT
TEMPERATURE
START
TEMPERATURE
MINIMUM FAN
SPEED
GAS OUTLET TEMPERATURE
FAN SPEED
GAS IN
COOLED GAS
OUT
WARM WATER
COOL WATER
TE
WATER COOLED GAS
AFTERCOOLER