11 – 5
Section 11 • Alarms, Trips, Status Information & Troubleshooting
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Alarm Message Cause(s) Notes
(A040) Alarm: Out of Range:
Discharge Recycle Control Pressure
Discharge Recycle Control Pressure
Instrument is Disconnected or Raw
value is less than 3.5 mA or Greater
than 20.5 mA.
Active if Controlling Discharge
Recycle Valve
(A041) Alarm: Out of Range: Oil
Separator Outlet Pressure
Oil Separator Outlet Pressure
Instrument is Disconnected or Raw
value is less than 3.5 mA or Greater
than 20.5 mA.
Active if Displaying Oil Separator
Outlet Pressure
(A042) Alarm: Unassigned
(A043) Alarm: Unassigned
(A044) Alarm: (Unassigned)
(A045) Alarm: (Unassigned)
(A046) Alarm: (Unassigned)
(A047) Alarm: (Unassigned)
(A048) Alarm: High Motor Phase A
Temperature
Phase A Motor Winding
Temperature exceeds Motor
Winding Temperature High Alarm
Setpoint
Active if Displaying Motor Winding
Temperatures
(A049) Alarm: High Motor Phase B
Temperature
Phase B Motor Winding Temperature
exceeds Motor Winding
Temperature High Alarm Setpoint
Active if Displaying Motor Winding
Temperatures
(A050) Alarm: High Motor Phase C
Temperature
Phase C Motor Winding Temperature
exceeds Motor Winding
Temperature High Alarm Setpoint
Active if Displaying Motor Winding
Temperatures
(A051) Alarm: Motor DE Bearing
Temperature
Drive End Motor Bearing
Temperature exceeds Motor Bearing
Temperature High Alarm Setpoint
Active if Displaying Motor Bearing
Temperatures
(A052) Alarm: Motor ODE Bearing
Temperature
Opposite Drive End Motor Bearing
Temperature exceeds Motor Bearing
Temperature High Alarm Setpoint
Active if Displaying Motor Bearing
Temperatures
(A053) Alarm: High Motor Vibration
- Sensor 1
Motor Vibration exceeds Motor
Vibration High Alarm Setpoint
(Sensor 1)
Active if Displaying Motor Vibration
Sensor 1
(A054) Alarm: High Motor Vibration
- Sensor 2
Motor Vibration exceeds Motor
Vibration High Alarm Setpoint
(Sensor 2)
Active if Displaying Motor Vibration
Sensor 2
(A055) Alarm: High Compressor
Vibration - Sensor 1
Compressor Vibration exceeds
Compressor Vibration High Alarm
Setpoint (Sensor 1)
Active if Displaying Compressor
Vibration Sensor 1
(A056) Alarm: High Compressor
Vibration - Sensor 2
Compressor Vibration exceeds
Compressor Vibration High Alarm
Setpoint (Sensor 2)
Active if Displaying Compressor
Vibration Sensor 2
(A057) Alarm: Inlet Scrubber High
Level
Inlet Scrubber High Liquid Level
Switch Activated
Active if Vane Type Inlet Scrubber is
Present