Section 11 • Alarms, Trips, Status Information & Troubleshooting
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Alarm Message Cause(s) Notes
(A017) Alarm: Low Process
Temperature
Process Temperature falls below
Process Temperature Low Alarm
Setpoint in Process Temperature
control or if displaying Process
Temperature.
Active if controlling or displaying
Process Temperature
(A018) Alarm: High Process
Temperature
Process Temperature exceeds
Process Temperature High Alarm
Setpoint in Process Temperature
control or if displaying Process
Temperature.
Active if controlling or displaying
Process Temperature
(A019) Alarm: (Unassigned)
(A020) Alarm: Low Liquid Refrigerant
Temperature
Liquid Refrigerant Temperature
falls below Liquid Refrigerant
Temperature Low Alarm Setpoint
if displaying Liquid Refrigerant
Temperature
Active if displaying Liquid Refrigerant
Temperature
(A021) Alarm: Low Suction Pressure
Stpt. 1
Setpoint 1 is selected and Suction
Pressure falls below Suction Pressure
Low Alarm.
(A022) Alarm: Low Suction Pressure
Stpt. 2
Setpoint 2 is selected and Suction
Pressure falls below Suction Pressure
Low Alarm.
(A023) Alarm: High Discharge
Pressure Stpt. 1
Setpoint 1 is selected and Discharge
Pressure falls below Discharge
Pressure High Alarm.
(A024) Alarm: High Discharge
Pressure Stpt. 2
Setpoint 2 is selected and Discharge
Pressure falls below Discharge
Pressure High Alarm.
(A025) Alarm: Low Net Oil Pressure
- Run
Net Oil Pressure (Oil Manifold
Pressure - Suction Pressure) falls
below Net Oil Pressure Low Alarm
Setpoint after prelube and warmup
are complete.
(A026) Alarm: Unassigned
(A027) Alarm: High Oil Filter
Differential - Start
Oil Filter Differential (Filter In
Pressure - Oil Manifold Pressure)
exceeds Oil Filter Differential - Start
High Alarm Setpoint when compres-
sor is running and before Oil Filter
Differential Start-Run Changeover
Timer expires.
(A028) Alarm: High Oil Filter
Differential - Run
Oil Filter Differential (Filter In
Pressure - Oil Manifold Pressure)
exceeds Oil Filter Differential - Run
High Alarm Setpoint when compres-
sor is running and after Oil Filter
Differential Start-Run Changeover
Timer expires.