6 – 9
Section 6 • Instrument Calibration
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Figure 6-9. Photo-chopper
Press down on Photo-
chopper to release tension
from motor shaft.
16. Quickly press and release the blue button on the
actuator one more time. The red LED will stop
ashing. The actuator is now calibrated and knows
the minimum and maximum positions of the slide
valve it controls. Now the capacity or volume chan-
nel of the PLC can be calibrated.
17. Use the down arrow button to move the actuator
towards its minimum position while watching the
mV readout on the screen. Discontinue pressing
the down arrow button when the mV reading is ap-
proximately 500 mV.
18. Now use the down arrow and up arrow buttons to
position the slide valve until a value close to 300 mV
is achieved. Then, press the “Set Min” button in the
capacity or volume slide valve window to tell the
controller that this is the minimum mV position.
19. Use the up arrow button to rotate the actuator to-
wards its maximum position while watching the
mV readout on the controller screen. Discontinue
pressing the up arrow button when the mV reading
of approximately 4800 mV is achieved.
20. Pulse the up arrow button to carefully move the
slide valve until the mV readout “saturates”, or
stops increasing. This is around 4800 mV Record
mV maximum reading.
21. Pulse the down arrow button until the mV just start
to decrease. (This is the point where the channel
drops out of saturation). Adjust mV value to 300
mV below recorded maximum mV.
22. Press the “Set Max” button.
23. Press the “Calibration Main” button to complete
calibration and exit the “Slide Calibration” screen.
The controller will automatically energize the ac-
tuator and drive it back to its minimum position
(below 5%) for pre-start-up.
NOTE
Now the current ‘Capacity” or the current ‘Volume”
value will be displayed on the Main screen and Slide
Calibration screen.
24. Gently lower the plastic cover over the top of the
actuator to where it contacts the base and O-ring
seal.
CAUTION
Do not over tigten screws. Failure to comply may
result in damage to equipment.
25. Check and make sure the cover is seated properly,
then gently tighten the four #10 screws.
26. Repeat procedure to calibrate other slide valve
actuator.