7 – 6
Section 7 • Compressor Control Setpoints
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
AUTO START/STOP
• Auto Start Pressure: When discharge pressure is
above this setpoint for the Auto Start Delay Time, the
compressor will be commanded to start.
• Auto Stop Pressure: When discharge pressure is be-
low this setpoint and capacity slide position is below
Minimum Slide Position for the Auto Stop Delay time,
the compressor will be commanded to stop.
• Auto Start Delay: Amount of time Auto Start pres-
sure must be met before the compressor will be com-
manded to start.
• Auto Stop Delay: Amount of time Auto Stop pressure
must be met before the compressor will be com-
manded to stop.
• Minimum Slide Position: Slide position must be be-
low this setpoint (indicating the compressor is fully
unloaded) before the compressor will be command-
ed to stop.
MAIN MOTOR VFD
• Max Speed Increase/Decrease per interval: This is the
maximum amount the main motor speed command
may be adjusted by every time through the Load/
Unload Cycle timer.
• Forced Unload Rate: If a forced unload condition ex-
ists and the main motor is running above 50% speed,
this is the rate it will decelerate until it reaches 50%
speed and the capacity slide begins unloading.