Section 2 • Operational Descriptions
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
OPERATING MODES
The loading and unloading of the compressor can be
con gured to operate in several ways, depending on the
needs of the site. This mode selection is made at the
“Start Menu” screen. There are four basic modes, de-
scribed below:
• Local-Auto: The compressor will adjust the position
of the capacity slide automatically using the control’s
capacity control algorithm. The target pressure or
temperature setpoint is set on the compressor’s lo-
cal HMI.
Local-Manual: The operator is in control of the capac-
ity slide from the local HMI. When in Local-Manual
mode, the operator controls the capacity slide po-
sition using increase/decrease pushbuttons on the
compressor overview screen.
Remote-Auto: The compressor will adjust the posi-
tion of the capacity slide automatically using the
control’s capacity control algorithm. The target
pressure or temperature setpoint is de ned by the
DCS/Central Controller via communications. (NOTE:
Control by Communications must be enabled to use
this mode.)
Remote-Manual: The capacity slide position is con-
trolled by a DCS or Central Controller. There are four
selectable methods of using Remote-Manual Control,
settable from the HMI’s con guration screen.
Caphold-Ethernet: Capacity slide valve position
commands are given by the central controller/
DCS via communications. (NOTE: Control by
Communications must be enabled to use this
method.)
Caphold-4-20mA Hardwired: Capacity slide
valve position commands are given by the cen-
tral controller/DCS via a 4-20mA analog signal.
The scaling is 4mA = 0% Capacity Slide Position,
20mA = 100% capacity slide position. Control by
Communications does not need to be enabled to
use this method.
Discrete Load/Unload – Ethernet: Capacity slide
valve increase and decrease commands are given
by the central controller/DCS via communica-
tions. (NOTE: Control by Communications must
be enabled to use this method.)
• Discrete Load/Unload – Hardwired: Capacity slide
valve increase and decrease commands are given
by the central controller/DCS via discrete hard-
wired inputs. Control by communications does
not need to be enabled to use this method.
In any of the above modes, all local safeties and load lim-
its still apply and will override external commands.
For safety reasons, remote mode is only enabled under
certain conditions. If these conditions are not met, the
machine will revert to local mode. To be able to enter
remote mode, the one of the following must be true:
Auto Mode Selected, Control By Communications
Enabled.
• Manual Mode Selected, Remote Manual Control
Source is Hardwired
Manual Mode Selected, Control by Communications
Enabled
In the event that the communications link between the
compressor PLC and the central controller/DCS is lost,
the action taken is selectable from the Con guration
screen. The machine will Trip or revert to Local mode
and continue to run depending on the selection.
The compressor PLC can be remotely commanded to
Local or Remote Mode if Control by Communications is
enabled.
NOTE
If a main motor VFD is being used for capacity control,
only discrete commands may be used in Remote-
Manual Control.
LOAD LIMITS AND FORCED UNLOADING
Reference example, Figure 2-5
To protect the compressor and process, the controller
will inhibit the compressor from loading or force it to un-
load if certain variables get outside of set ranges. Three
load limiting variables are continuously monitored:
Low Suction Pressure
High Discharge Pressure
High Main Motor Amps
There are independent Load Limit Setpoints speci c to
“Setpoint 1” and “Setpoint 2” setpoint groups, allow-
ing load limits to be speci c to unique operating condi-
tions. For each of the three variables, three setpoints are
active:
Inhibit Loading: when this setpoint is reached, the
compressor will not be allowed to continue loading.
Unload at: when this setpoint is reached, the capac-
ity slide will move in the decrease direction continu-
ously (forced unload) until the “Unload To” setpoint
is reached.
Unload To: this is the setpoint at which the capac-
ity slide will stop unloading from a forced unload
condition.