2 – 24
Section 2 • Operational Descriptions
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
level switch.
The drain pump or solenoid valve will turn off
when the liquid level in the scrubber drops to the
“Cutout” level switch.
• Dual pumps may be used. Selection of Pump A or
B is made in the Con guration screen.
BUILDING ENCLOSURE DEVICES
If the compressor unit is mounted inside a building en-
closure, the following are monitored/controlled:
Space Heater – maintains a desired temperature
range inside the enclosure. Space Heater ON and
OFF setpoints are in the compressor control setpoint
screens.
Exhaust Fans – maintains a desired temperature
range inside the enclosure. Exhaust Fan ON and OFF
setpoints are in the compressor control setpoint
screens. If the methane detector %LEL reaches alarm
level, the exhaust fans will also turn on until the alarm
is cleared.
Methane Detector – monitors the %LEL of the air
inside the enclosure. Generates an alarm and trip.
Alarm and trip setpoints are settable in the Alarm and
Trip Setpoints screen.
• Smoke Detector – If triggered by smoke within the
enclosure, will shut down the compressor and trip
the compressor emergency stop.
PERIODIC SLIDE VALVE EXERCISE
If used, the periodic slide valve exercise function moves
the slide valves if they have not moved for a settable
time to prevent them from sticking. This function ap-
plies to both capacity and volume slides.
If the compressor is running, and the capacity slide
has not moved for the settable amount of time, the
exercise function will increase capacity slide posi-
tion by 10% (if its current position is less than 50%)
or decrease capacity slide position by 10% (if its cur-
rent position is greater than 50%). Once the slide has
been moved, the exercise function ‘releases’ slide to
operate to maintain desired pressure or temperature.
If the compressor is running, and the volume slide
has not moved for the settable amount of time, the
exercise function will increase volume slide position
by 10% (if its current position is less than 50%) or de-
crease volume slide position by 10% (if its current po-
sition is greater than 50%). Once the slide has been
moved, the volume slide will return to the command-
ed position calculated by the controller.