11 – 9
Section 11 • Alarms, Trips, Status Information & Troubleshooting
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Trip Message Cause(s) Notes
(T001) Trip: MCR Not Energized/E-
Stop Active
Emergency Stop Button on PLC
panel Pressed, Loss of Power
(T002) Trip: PLC to Central Comms
Faulted
Loss of Communication with DCS/
Central - Settable Communications
Watchdog Timer Expired. (Action on
Comm Failure = Trip)
Watchdog Active if Control by
Communications is selected
(T003) Trip: High Main Motor Amps Main Motor Amps exceeds Motor
Amps High Trip setpoint.
(T004) Setpoint out of Range - See
Menu Screen
(T005) Trip: False Start Detected Main motor was detected running
when not commanded to run.
(T006) Trip: Low Separator Oil Level Oil Separator Level Switch has
opened indicating drop in Separator
Oil Level. (Trip action Selected)
Active if Oil Separator Level Switch
Selected.
(T007) Trip: Faulted I/O Module
Connection or Module Type
(T008) Trip: Main Motor Starter Fault Main Motor Starter Fault Contact has
opened.
(T009) Trip: Main Motor Feedback
Fault/Overload
Main Motor is commanded to run,
Running con rmation not received.
(T010) Trip: Main Motor Shunt Trip
Activated
Shutdown Active.
Note: Output energized to activate
a power removal device to protect
the compressor when a false start is
detected.
(T011) Trip: Low Suction
Temperature
Suction Temperature falls below
"Suction Temperature" Low Trip
Setpoint.
(T012) Trip: High Discharge
Temperature
Discharge Temperature exceeds
"Discharge Temperature" High Trip
Setpoint.
(T013) Trip: Low Oil Separator
Temperature - Start
Separator Oil Temperature is Below
"Separator Oil Temperature - Start"
Low Trip Setpoint when compres-
sor is off or Oil Separator Start-Run
Timer has not expired.
(T014) Trip: Low Oil Separator
Temperature - Run
Separator Oil Temperature is Below
"Separator Oil Temperature - Run"
Low Trip Setpoint After Oil Separator
Start-Run Timer has expired.
Trip Listing
Table 11-2. Trip Listing