Section 12 • Communications with a Central Controller/DCS
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Interface Tag Description
BOOL_OUT[23].10 (S075) Status: Condenser Fan 9 FORCED ON
BOOL_OUT[23].11 (S076) Status: Condenser Fan 10 FORCED ON
BOOL_OUT[23].12 (S077) Status: Condenser Water Valve FORCED ON
BOOL_OUT[23].13 (S078) Status: VPLUS Pump FORCED ON
BOOL_OUT[23].14 (S079) Status: Liquid Injection Valve Air SOV FORCED ON
BOOL_OUT[23].15 (S080) Status: Discharge Recycle Air SOV FORCED ON
BOOL_OUT[23].16 (S081) Status: Oil Mixing Valve FORCED ON
BOOL_OUT[23].17 (S082) Status: Oil Injection Valve FORCED ON
BOOL_OUT[23].18 (S083) Status: Alarm Indication FORCED ON
BOOL_OUT[23].19 (S084) Status: Trip Indication FORCED ON
BOOL_OUT[23].20 (S085) Status: Oil Separator Heaters FORCED ON
BOOL_OUT[23].21 (S086) Status: Suction Oil SOV FORCED ON
BOOL_OUT[23].22 (S087) Status: Gas EQ SOV FORCED ON
BOOL_OUT[23].23 (S088) Status: Economizer SOV FORCED ON
BOOL_OUT[23].24 (S089) Status: Hotgas SOV FORCED ON
BOOL_OUT[23].25 (S090) Status: Venturi Oil Recovery SOVs FORCED ON
BOOL_OUT[23].26 (S091) Status: Inlet Scrubber Drain Pump/SOV FORCED ON
BOOL_OUT[23].27 (S092) Status: Inlet Scrubber Backup SOV FORCED ON
BOOL_OUT[23].28 (S093) Status: Outlet Scrubber Drain Pump/SOV FORCED ON
BOOL_OUT[23].29 (S094) Status: Outlet Scrubber Backup SOV FORCED ON
BOOL_OUT[23].30 (S095) Status: Enclosure Vent Fans FORCED ON
BOOL_OUT[23].31 (S096) Status: Enclosure Heaters FORCED ON
BOOL_OUT[24].0 (S097) Status: Evap Condenser Pump FORCED ON
BOOL_OUT[24].1 (S098) Status: NOT USED
BOOL_OUT[24].2 (S099) Status: EPCS SOV FORCED ON
BOOL_OUT[24].3 (S100) Status: Oil Cooler STBY Heaters FORCED ON
BOOL_OUT[24].4 (S101) Status: Alarm Horn FORCED ON
BOOL_OUT[24].5 (S102) Status: Stacklight - Amber FORCED ON
BOOL_OUT[24].6 (S103) Status: Stacklight - Red FORCED ON
BOOL_OUT[24].7 (S104) Status: INLET SCRUBBER - PUMP 2 FORCED ON
BOOL_OUT[24].8 (S105) Status: OUTLET SCRUBBER - PUMP 2 FORCED ON
BOOL_OUT[24].9 (S106) Status: OIL DRAIN SV FORCED ON
BOOL_OUT[24].10 (S107) Status: Economizer Port 2 FORCED ON
BOOL_OUT[24].11 (S108) Status: Supplemental Shutdown FORCED ON
BOOL_OUT[24].12 (S109) Status: User MGR Logged In
BOOL_OUT[24].13 (S110) Status: Setpoint 1 Active
BOOL_OUT[24].14 (S111) Status: Setpoint 2 Active
BOOL_OUT[24].15 (S112) Status: Maintenance Due
BOOL_OUT[24].16 (S113) Status: Aftercooler 1 Valve Forced
BOOL_OUT[24].17 (S114) Status: Aftercooler 2 Valve Forced
BOOL_OUT[24].18 (S115) Status: Capacity Slide Exercise Active