11 – 4
Section 11 • Alarms, Trips, Status Information & Troubleshooting
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Alarm Message Cause(s) Notes
(A029) Alarm: Low Oil Pressure
- Start
Net Oil Pressure (Oil Manifold
Pressure - Suction Pressure) falls
below Net Oil Pressure Low Alarm
Setpoint after before Warmup is
complete
(A030) Alarm: (Unassigned)
(A031) Alarm: Out of Range: Oil
Cooler Inlet Temp
Oil Cooler Inlet Temperature
Instrument is Disconnected or Raw
value is less than 3.5 mA or Greater
than 20.5 mA (if using a 4-20mA
Temperature Transmitter).
Active if Displaying Oil Cooler Inlet
Temperature
(A032) Alarm: Out of Range: Oil
Cooler Outlet Temp
Oil Cooler Outlet Temperature
Instrument is Disconnected or Raw
value is less than 3.5 mA or Greater
than 20.5 mA (if using a 4-20mA
Temperature Transmitter).
Active if Controlling an Oil Cooler
or Displaying Oil Cooler Outlet
Temperature
(A033) Alarm: Out of Range:
Condensing Pressure
Condensing Pressure Instrument is
Disconnected or Raw value is less
than 3.5 mA or Greater than 20.5
mA.
Active if Controlling a Condenser
(A034) Alarm: Out of Range:
Aftercooler 1 Outlet Temp
Aftercooler 1 Out Temperature
Instrument is Disconnected or Raw
value is less than 3.5 mA or Greater
than 20.5 mA (if using a 4-20mA
Temperature Transmitter).
Active if Controlling Aftercooler 1
(A035) Alarm: Out of Range:
Aftercooler 2 Outlet Temp
Aftercooler 2 Out Temperature
Instrument is Disconnected or Raw
value is less than 3.5 mA or Greater
than 20.5 mA (if using a 4-20mA
Temperature Transmitter).
Active if Controlling Aftercooler 2
(A036) Alarm: Out of Range: Inlet
Scrubber Inlet Pressure
Inlet Scrubber Inlet Pressure
Instrument is Disconnected or Raw
value is less than 3.5 mA or Greater
than 20.5 mA.
Active if Inlet Scrubber is Present
(A037) Alarm: Out of Range: Inlet
Scrubber Outlet Pressure
Inlet Scrubber Outlet Pressure
Instrument is Disconnected or Raw
value is less than 3.5 mA or Greater
than 20.5 mA.
Active if Inlet Scrubber is Present
(A038) Alarm: Out of Range: Outlet
Scrubber Inlet Pressure
Outlet Scrubber Inlet Pressure
Instrument is Disconnected or Raw
value is less than 3.5 mA or Greater
than 20.5 mA.
Active if Outlet Scrubber is Present
(A039) Alarm: Out of Range: Outlet
Scrubber Outlet Pressure
Outlet Scrubber Outlet Pressure
Instrument is Disconnected or Raw
value is less than 3.5 mA or Greater
than 20.5 mA.
Active if Outlet Scrubber is Present