Section 2 • Operational Descriptions
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
START
STEP #
TARGET
TEMPERATURE OR
PRESSURE
STEP #
TARGET
DEADBAND
DEADBAND
TEMPERATURE OR
PRESSURE
1 STEP ADDED
EVERY CYCLE OF
CYCLE TIMER
NO STEPS ADDED
OR REMOVED
1 STEP REMOVED
EVERY CYCLE OF
CYCLE TIMER
FANS TURNING ON FANS TURNING OFF
Figure 2-11. Operational Diagram - All Air Cooled Oil Coolers (Step Type)
AIR COOLED OIL COOLER (STEP TYPE)
Reference Figure 2-11
If installed, the step type air cooled oil cooler is a heat
exchanger that uses multiple fans to control the oil tem-
perature at its outlet.
The controller starts and stops fans in a sequence to con-
trol the temperature at the outlet of the oil cooler. When
the temperature of the oil at the outlet of the cooler
exceeds the desired temperature plus a deadband, fans
will be turned on after a time delay to add more cooling.
When outlet temperature drops below the desired tem-
perature minus a deadband, fans will be turned off after
a time delay.
• When the compressor is stopped, all oil cooler fans
are turned off.
• When the compressor is running and the oil cooler
TE