Section 5 • Configuration - Supervisor Level
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
PROCESS VARIABLE SOURCE
De nes the pressure data used to control the capacity
slide.
Local Hard-Wired Transducer – capacity slide and
auto start/stop is controlled by the suction/discharge
pressure transducer mounted on the compressor
unit or package.
Common/Remote – capacity slide and auto start/
stop is controlled by suction/discharge header pres-
sure data from a DCS/Central Controller. On loss of
communications, the compressor control will ei-
ther shut down the compressor or revert to the lo-
cal transducer based on the “Communication Fault
Action” setting.
CONTROL MODE
De nes the pressure or temperature the compres-
sor will try to maintain. See Section X “Operational
Descriptions” for more information on the functionality
of each control mode.
SELECT SETPOINT 1 / 2
Determines which group of setpoints is active – used
when a machine could be run in 2 unique sets of oper-
ating conditions, ex. High/low stage swing compressor.
AUTO START-STOP
Enables or Disables the auto start-stop function. See
Section X “Operational Descriptions” for more informa-
tion on the functionality of the auto start-stop function.
OIL PUMP OPERATION
Determines operation of the oil pump.
Full Time – the oil pump will run continuously when
the compressor is running.
Part Time – the oil pump will run at compressor start-
up but will stop if there is enough differential pres-
sure from discharge-suction.
See the compressor start sequence in Section X
“Operational Descriptions” for more information on the
functionality of the oil pump.
MOTOR RTDs
Selects if Motor Winding and Bearing Temperatures are
being monitored by the controller.
SCHEDULED MAINTENANCE TIMER
Optional function that can be set up to display main-
tenance reminders after a settable amount of run-
time. When the accumulated runtime reaches the set
“Maintenance Interval” time, a status message will ap-
pear on the overview and menu screens indicating the
text entered in the “Message” eld.
INLET / OUTLET SCRUBBER PUMP A / B
If the inlet and/or outlet scrubbers include dual conden-
sate pumps, this selection determines which pump is
active.
CHANGE PASSWORD
Pressing the “Change Password” button opens the
“Change Password” pop-up screen, see Figure 5-3 To
change a password on an account, the user must be
logged in under that account.
Figure 5-3. Change Password Pop-Up Screen - Supervisor Level