Section 2 • Operational Descriptions
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Unload Interval Time – Cycle time for calculating ca-
pacity slide position adjustment when the controller
is calling for the machine to decrease capacity slide
position. Where the Load Interval Time is T2, the
control will make an adjustment calculation every T2
seconds.
Max Load Adjustment per Interval – Maximum posi-
tion adjustment that can be made when the control
is calling for the machine to increase capacity slide
position. Where the Maximum Load Adjustment is
A1, the capacity slide position will increase by A1%
every cycle of the Load Interval Timer when outside
the bandwidth range. When inside the bandwidth
range, the capacity slide position adjustment will be
a percentage of A1.
Max Unload Adjustment per Interval – Maximum po-
sition adjustment that can be made when the control
is calling for the machine to decrease capacity slide
position. Where the Maximum Unload Adjustment
is A2, the capacity slide position will increase by A2%
every cycle of the Unload Interval Timer when out-
side the bandwidth range. When inside the band-
width range, the capacity slide position adjustment
will be a percentage of A2.
When the compressor is stopped, the capacity slide will
return to its minimum position.
SUCTION PRESSURE & PROCESS TEMPERATURE
*EVERY CYCLE OF INTERVAL TEMPERATURE, MAX LOAD
ADJUSTMENT IS MADE (CAP INCREASE)
60 PSIG
*EVERY CYCLE OF INTERVAL TIMER, CAPACITY COMMAND WILL
INCREASE BY CALCULATED AMOUNT, PROPORTIONAL TO ERROR
51 PSIG
*EVERY CYCLE OF INTERVAL TIMER, CAPACITY COMMAND WILL
DECREASE BY CALCULATED AMOUNT, PROPORTIONAL TO ERROR
1 PSID (NO ADJUSTMENT)
49 PSIG
45 PSIG
*EVERY CYCLE OF INTERVAL TIMER, MAX UNLOAD
ADJUSTMENT IS MADE (CAPACITY DECREASE)
DISCHARGE PRESSURE
*EVERY CYCLE, UNLOAD BY MAX UNLOAD ADJUSTMENT
105 PSIG
*EVERY CYCLE OF INTERVAL TIMER, MAKE
PROPORTIONAL ADJUSTMENT (CAPACITY DECREASE)
102 PSIG
*EVERY CYCLE OF INTERVAL TIMER, MAKE
PROPORTIONAL ADJUSTMENT (CAPACITY INCREASE)
2 PSID (NO ADJUSTMENT)
98 PSIG
90 PSIG
*EVERY CYCLE, LOAD BY MAX LOAD ADJUSTMENT
PRESSURE OR TEMPERATUREPRESSURE
UPPER BANDWIDTH
5 PSID
TARGET (100 PSIG)
LOWER BANDWIDTH
10 PSID
TARGET (50 PSIG)
UPPER PROPORTIONAL BAND
(10 PSID)
UPPER PROPORTIONAL DEADBAND
LOWER PROPORTIONAL DEADBAND
LOWER PROPORTIONAL BAND
(5 PSID)
1 PSID (NO ADJUSTMENT)
2 PSID (NO ADJUSTMENT)
UPPER PROPORTIONAL DEADBAND
LOWER PROPORTIONAL DEADBAND
Figure 2-2. Capacity Slide Control Diagram (Example)