Section 11 • Alarms, Trips, Status Information & Troubleshooting
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Alarm Message Cause(s) Notes
(A001) Alarm: (Unassigned)
(A002) Alarm: PLC to Central Comms
Faulted
Loss of Communication with DCS/
Central - Settable Communications
Watchdog Timer Expired. (Alarm
and Revert to Local Selected on
Communication Failure.)
Watchdog Active if Control by
Communications is selected
(A003) Alarm: High Main Motor
Amps
Main Motor Amps exceeds Motor
Amps High Alarm setpoint.
(A004) Alarm: (Unassigned)
(A005) Alarm: (Unassigned)
(A006) Alarm: Low Separator Oil
Level
Oil Separator Level Switch has
opened indicating drop in Separator
Oil Level. (Alarm action Selected)
Active if Oil Separator Level Switch
Selected.
(A007) Alarm: Not Assigned
(A008) Alarm: Not Assigned
(A009) Alarm: Not Assigned
(A010) Alarm: Not Assigned
(A011) Alarm: Low Suction
Temperature
Suction Temperature falls below
"Suction Temperature" Low Alarm
Setpoint.
(A012) Alarm: High Discharge
Temperature
Discharge Temperature exceeds
"Discharge Temperature" High Alarm
Setpoint.
(A013) Alarm: Low Oil Separator
Temperature - Start
Separator Oil Temperature is Below
"Separator Oil Temperature - Start"
Low Alarm Setpoint when compres-
sor is off or Oil Separator Start-Run
Timer has not expired.
(A014) Alarm: Low Oil Separator
Temperature - Run
Separator Oil Temperature is
Below "Separator Oil Temperature
- Run" Low Alarm Setpoint After
Oil Separator Start-Run Timer has
expired.
(A015) Alarm: Low Oil Injection
Temperature
Oil Injection Temperature is Below
"Oil Injection Temperature" Low
Alarm Setpoint after compressor has
completed pre-lube and warm up
stages.
(A016) Alarm: High Oil Injection
Temperature
Oil Injection Temperature exceeds
"Oil Injection Temperature" High
Alarm Setpoint
Table 11-1. Alarm Listing
Alarm Listing
The following table shows all possible alarms and trips and possible causes. Some alarms and trips are application
speci c, and do not apply unless a speci c option is selected.
To reset alarms or trips press the “Alarm Reset” Button on the overview screen. If the condition is cleared, the alarm
will reset. If the condition is not cleared, the alarm will remain active.