Section 11 • Alarms, Trips, Status Information & Troubleshooting
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Status Messages and Compressor State Indicator
Status messages are used to indicate compressor status information to the user. Status messages are used to inform
the user of any of the following conditions.
• Anti-Recycle Timer is active
• Compressor is in standby mode and is waiting for one or more conditions to be met
• State of the Compressor Startup Sequence
• Load Limits and Forced Unloading
• Slide Calibration is active
Compressor PLC has automatically reverted to Local-Auto mode on loss of communications with central con-
troller or DCS (if this function is enabled)
• A user is logged in
• An output is forced
• Scheduled Maintenance is due (if this function is enabled)
• Slide valve exercising is active (if this function is enabled)
Status messages are shown in a green scrolling banner at the top of the overview and menu screens.
Figure 11-3. Alarm/Trip/Status Bars (Main Menu Screen)
Status Message Notes
(S001) Status: Compressor Stopped Displayed in the Event List only
(S002) Status: Compressor Started Displayed in the Event List only
(S003) Status: NOT USED
(S004) Status: True Anti-Recycle Active: Remaining:
XX:XX
Shows remaining anti-recycle time
(S005) Status: NOT USED
(S006) Status: Waiting to Start: Discharge-Suction Not
Equalized
Compressor PLC is waiting for compressor Discharge-
Suction to be equalized to within a settable differential
before the compressor will start.
(S007) Status: Waiting to Start: Remote Run Permissive
Input
Compressor PLC is waiting for a contact closure on the
remote run permissive input before the compressor
will start
(S008) Status: Waiting to Start: Soft Run Permissive from
DCS/Central
Compressor PLC is waiting for a run command from
the central controller or DCS (if control by communica-
tions is enabled)
(S009) Status: Auto Cycle Stop - Suction Pressure Auto Start-Stop function is enabled and "Stop" Pressure
has been reached.
(S010) Status: Auto Cycle Stop - Process Temperature Auto Start-Stop function is enabled and "Stop"
Temperature has been reached.
Table 11-3. Status Listing