Section 2 • Operational Descriptions
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
The following are optional compressor unit and package
items that can be controlled or monitored, speci c to
gas compression applications:
Up to 2 Aftercoolers
• Air Cooled Step Type
• Air Cooled VFD Type
• Water Cooled
• Inlet Scrubber
• Pressure Drop across vessel
• Condensate Drain
• Low/High Level Safety Switches
• Outlet Scrubber
• Pressure Drop across vessel
• Condensate Drain
• Low/High Level Safety Switches
Discharge Recycle Valve
Building Enclosure Devices
• Space Heaters
• Roof Exhaust Fans
• Methane %LEL Detector
Oil Separator Gas Outlet Temperature – Temperature
of the gas measured at the discharge of the oil sepa-
rator. Used to monitor the temperature of the gas
relative to dew point. If the compressor is warm and
this temperature is too low, the controller will gener-
ate an alarm.
• Oil Separator Gas Outlet Pressure – Pressure of the
gas measured at the discharge of the oil separator.
Used to monitor the pressure drop across the co-
alescing elements of the oil separator. When pres-
sure drop is too high, the controller will generate an
alarm.
Reheater Vessel and shell/tube side Temperatures –
Temperature of the gas measured at the discharge of
both the shell and tube sides of the reheater vessel.
Periodic Slide Valve Exercising
Operational Descriptions and
Diagrams
STARTING OF THE COMPRESSOR/PERMISSIVES
To run the compressor, it must me started from the
“Start Menu” screen on the control panel HMI. Pressing
“Unit Start” in the “Start Menu” screen will initiate a start
if all permissives to initiate a start are met. To initiate a
start, the following conditions must be met:
Control Power is ON (Emergency Stop button is not
pressed, Master Control Relay is energized or activat-
ed by remote device, indicated by pilot light on front
of panel)
No Active Trips
When a start is initiated, the compressor will start if all
permissives to run the compressor are met. If all permis-
sives to run the compressor are not met, the control will
wait in a “standby” mode until all conditions to run are
satis ed. Any condition that the control is waiting on
is annunciated on the overview and menu screens and
logged in the Event List. To begin the compressor start-
up sequence, the following conditions must be met:
Control Power is ON (Emergency Stop button is not
pressed and Master Control Relay is energized, indi-
cated by pilot light on front of panel)
No Active Trips
Compressor start has been initiated by pressing “Unit
Start” in the “Start Menu” screen.
Remote Permissive input is ON
Soft run permissive from the DCS/Central Controller
is ON (if control by communications selected)
Anti-Recycle Timer is not active
Suction – Discharge is equalized to within a settable
differential
Auto Start control is calling for the compressor to
start, if Auto Start/Stop is Enabled.
If a start is initiated at the compressor, the machine state
indicator will indicate “Standby” and the condition the
compressor is waiting on will be annunciated on the
overview and menu screens.