Section 2 • Operational Descriptions
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Overview
The following are standard equipment on all compressor
units or packages that can be controlled or monitored:
Suction Pressure – Pressure of the gas measured at
the inlet of the compressor.
Discharge Pressure – Pressure of the gas at the outlet
of the compressor. Measured at the oil separator.
Oil Filter Inlet Pressure – Pressure of oil measured at
the inlet of the oil lter(s).
Oil Manifold Pressure (Oil Filter Out) – Pressure of oil
measured after the oil lter(s).
Prelube Oil Pressure (at compressor start, Oil
Manifold – Discharge Pressure)
Net Oil Pressure (when compressor running, Oil
Manifold – Suction Pressure)
Suction Temperature – Temperature of the gas mea-
sured at the inlet of the compressor.
Discharge Temperature – Temperature of the gas and
oil mixture at the outlet of the compressor
Separator Oil Temperature – Temperature of the oil in
the oil separator vessel.
Oil Injection Temperature – Temperature of the oil as
it goes into the compressor.
Capacity Slide Valve Position - % Travel of the capacity
slide valves.
Volume Slide Valve Position - % Travel of the volume
slide valves.
• Main Motor Amperage – Current draw by the main
motor.
Separator Oil Heaters
Compressor Main Motor
Oil Pump (Full Time or Part Time Selectable)
Selectable groups of setpoints for varying operating
conditions
The following are additional software controls available
that are native to all compressor units controlled by the
compressor PLC:
Monitoring of Instrument Data, Alarms, Trips, and
Machine Status by DCS/Central Controller
Compressor Capacity control setpoint from DCS/
Central Controller
Control of Compressor Loading/Unloading from
DCS/Central Controller
Capacity control on External Pressure Transducer
data from DCS/Central Controller
Auto Start/Stop based on process pressure or
temperature
Control of Local/Remote from DCS/Central Controller
Setpoint Group Selectable from DCS/Central
Controller
Remote Starting and Stopping of the Compressor
The following are optional compressor unit-speci c
items that can be controlled or monitored:
Compressor Main Motor VFD Control
Main Motor Winding Temperatures
Main Motor Bearing Temperatures
Motor Vibration (up to 2 sensors)
Compressor Vibration (up to 2 sensors)
Oil Separator Level Switch
Suction Oil Injection Solenoid Valve (Used on Models
2401-3001)
Suction-Discharge Equalizing Solenoid Valve
Oil Drain Solenoid Valve
Oil Separator Outlet Pressure, to calculate pressure
drop across coalescing elements of oil separator
2-Way Oil Mixing Valve
Air Cooled Oil Cooler (Step or VFD Type)
Oil Cooler Inlet/Outlet Temperatures
Oil Cooler Standby Heater
The following are optional compressor unit and package
items that can be controlled or monitored, speci c to re-
frigeration applications:
Air Cooled Condenser (Step Type or VFD Type)
Evaporative Air Cooled Condenser
Water Cooled Condenser
Oil Injection Control Valve
Liquid Injection Oil Cooling
VPLUS Liquid Oil Cooling
Economizer Port Solenoid Valves (single or dual)
Hotgas Bypass Solenoid
Venturi Oil Recovery
Liquid Refrigerant Temperature – Temperature of the
liquid refrigerant in the chiller.
Process Temperature – Temperature of the process
uid leaving the chiller