Section 9 • Step and PID Device Control Screens
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Figure 9-2. Oil Cooler (VFD Type) Screen
OIL COOLER (VFD TYPE) SETPOINTS
Start Oil Cooler Above: De nes the temperature the
oil cooler fans will come on at minimum speed.
Target Oil Cooler Outlet Temperature: De nes the de-
sired temperature of oil at the outlet of the oil cooler.
The oil cooler fan speed will adjust to maintain this
temperature.
• Deadband: Range above and below setpoint where
the controller will not make adjustments to fan speed.
PID Tuning: PID Calculations displayed to aid in tun-
ing the PID loop.
Loop Update Time: De nes the PID controller loop
time. The PID calculation will update every cycle of
the loop update timer.
Proportional Gain (Kp): De nes the Proportional
Constant of the PID calculation.
Integral Gain (Ki): De nes the Integral Constant of
the PID calculation.
Derivative Gain (Kd): De nes the Derivative Constant
of the PID Calculation.
Minimum Speed: De nes the minimum oil cooler fan
speed.
Plenum Heater ON Temp: De nes the oil cooler out-
let temperature at which the oil cooler plenum heater
turns ON (if used).
Plenum Heater OFF Temp: De nes the oil cooler out-
let temperature at which the oil cooler plenum heater
turns OFF (if used).
• Oil Cooler Fan VFD Force: Allows the user to manu-
ally force the oil cooler fan(s) to a settable speed.
Activating the Oil Cooler Fan VFD Force pushbutton
will command the oil cooler fan(s) to go to the set
speed, and will override calculations from the PID
Controller.