Section 11 • Alarms, Trips, Status Information & Troubleshooting
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Trip Message Cause(s) Notes
(T028) Trip: High Oil Filter
Differential - Run
Oil Filter Differential (Filter In
Pressure - Oil Manifold Pressure)
exceeds Oil Filter Differential - Run
High Trip Setpoint when compres-
sor is running and after Oil Filter
Differential Start-Run Changeover
Timer expires.
(T029) Trip: Low Oil Pressure - Start Net Oil Pressure (Oil Manifold
Pressure - Suction Pressure) falls
below Net Oil Pressure Low Trip
Setpoint after before Warmup is
complete
(T030) Trip: (Unassigned)
(T031) Trip: Out of Range: Suction Pr Suction Pressure Instrument is
Disconnected or Raw value is less
than 3.5 mA or Greater than 20.5
mA
(T032) Trip: Out of Range: Discharge
Pr
Discharge Pressure Instrument is
Disconnected or Raw value is less
than 3.5 mA or Greater than 20.5
mA
(T033) Trip: Out of Range: Manifold
Pr
Oil Manifold Pressure Instrument is
Disconnected or Raw value is less
than 3.5 mA or Greater than 20.5
mA.
(T034) Trip: Out of Range: Filter Inlet
Pr
Oil Filter Inlet Pressure Instrument
is Disconnected or Raw value is less
than 3.5 mA or Greater than 20.5
mA
(T035) Trip: Out of Range: Suction
Temp
Suction Temperature Instrument is
Disconnected or Raw value is less
than 3.5 mA or Greater than 20.5
mA (if using a 4-20mA Temperature
Transmitter).
(T036) Trip: Out of Range: Discharge
Temp
Discharge Temperature Instrument
is Disconnected or Raw value is less
than 3.5 mA or Greater than 20.5
mA (if using a 4-20mA Temperature
Transmitter).
(T037) Trip: Out of Range: Oil Sep
Temp
Separator Oil Temperature
Instrument is Disconnected or Raw
value is less than 3.5 mA or Greater
than 20.5 mA (if using a 4-20mA
Temperature Transmitter).
(T038) Trip: Out of Range: Oil
Injection Temp
Oil Injection Temperature
Instrument is Disconnected or Raw
value is less than 3.5 mA or Greater
than 20.5 mA (if using a 4-20mA
Temperature Transmitter).