Section 9 • Step and PID Device Control Screens
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Figure 9-11. Liquid Injection (VPLUS Pump) Screen
LIQUID INJECTION (VPLUS PUMP) SETPOINTS
Start Pump At: De nes the temperature at which the
VPLUS pump will start at its minimum speed.
Target Discharge Temperature: De nes the desired
temperature of gas and oil discharging from the com-
pressor. The VPLUS pump will adjust speed to main-
tain this temperature.
• Deadband: Range above and below setpoint where
the controller will not make adjustments to the
VPLUS pump speed.
Oil Separator Override Temperature: Separator Oil
Temperature must be above this temperature for the
VPLUS pump to operate.
PID Tuning: PID Calculations displayed to aid in tun-
ing the PID loop.
Loop Update Time: De nes the PID controller loop
time. The PID calculation will update every cycle of
the loop update timer.
Proportional Gain (Kp): De nes the Proportional
Constant of the PID calculation.
Integral Gain (Ki): De nes the Integral Constant of
the PID calculation.
Derivative Gain (Kd): De nes the Derivative Constant
of the PID Calculation.
Minimum Pump Speed: De nes the minimum speed
of the VPLUS pump.
VPLUS Pump Force: Allows the user to manually force
the VPLUS pump to a settable speed. Activating the
VPLUS Pump Force pushbutton will command the
VPLUS pump to go to the set speed, and will override
calculations from the PID Controller.