9 – 6
Section 9 • Step and PID Device Control Screens
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Figure 9-6. Water Cooled Aftercooler Screen
WATER COOLED AFTERCOOLER SETPOINTS
• Open Valve Above: De nes the temperature the af-
tercooler water supply valve will open to minimum
position.
Target Aftercooler Outlet Temperature: De nes the
desired temperature of gas at the outlet of the after-
cooler. The aftercooler water supply valve position
will adjust to maintain this temperature.
• Deadband: Range above and below setpoint where
the controller will not make adjustments to water
supply valve positon.
PID Tuning: PID Calculations displayed to aid in tun-
ing the PID loop.
Loop Update Time: De nes the PID controller loop
time. The PID calculation will update every cycle of
the loop update timer.
Proportional Gain (Kp): De nes the Proportional
Constant of the PID calculation.
Integral Gain (Ki): De nes the Integral Constant of
the PID calculation.
Derivative Gain (Kd): De nes the Derivative Constant
of the PID Calculation.
Minimum Valve Open: De nes the minimum water
supply valve position.
Aftercooler Valve Force: Allows the user to manu-
ally force the aftercooler water supply valve to a set-
table position. Activating the Aftercooler Valve Force
pushbutton will command the aftercooler water sup-
ply valve to go to the set position, and will override
calculations from the PID Controller.