Section 6 • Instrument Calibration
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Figure 6-7. Slide Calibration Screen (In Calibration Mode)
2. Remove screws securing actuator cover to actuator
assembly. As a reference see Figure 6-8.
CAUTION
Wires are attached to the connector on the actuator
cover. Handle actuator cover with care to prevent
damage to wires. Failure to comply may result in
damage to equipment.
3. Carefully lift actuator cover from actuator assembly
and tilt towards the Turck connector. Raise cover
high enough to be able to press the blue calibration
button and be able to see the red LED on top of the
assembly.
4. From main screen:
Press Main Menu > Instrument Calibration >
Calibrate Slides
5. Logging on with high-level access will prompt
the Calibrate button to appear on Instrument
Calibration Overview screen.
CALIBRATE SLIDE VALVE ACTUATORS
Slide valve actuators must be installed prior to calibra-
tion. Refer to Slide Valve Actuator Installation procedure
in VSG/VSSG Compressor Unit manual (35391SSG). The
following steps pertain to calibrating one slide valve ac-
tuator. Repeat procedure to calibrate other slide valve
actuator.
WARNING
After stopping the compressor, allow the compressor
and surrounding components to cool down prior
to servicing. Failure to comply may result in serious
injury.
CAUTION
Do not calibrate in direct sunlight. Failure to comply
may result in damage to equipment.
To calibrate optical actuators, proceed with the follow-
ing steps.
1. Stop compressor unit and allow to cool.