Single Screw Compressor PLC Operation Manual •Vilter/Emerson • 35391CM
Section 1 • General Information
Incoming power enters on the left bottom wall of the
PLC control enclosure. Route these conductors in the
space between the sub-panel and inside wall of the
enclosure.
DC control, analog and communications or network
wiring enters on the right bottom wall of the PLC con-
trol enclosure.
Wiring external to the panel per NEC (NFPA 70), ANSI
12.12.01 and UL-598A.
Panel construction and wiring per UL-508A for all
panels and ANSI 12.12.01 and UL-698A for hazardous
locations.
Electrical transmission, control, and alarm wiring
shall be stranded copper no smaller than #14 AWG.
Use JIC color code, unless otherwise noted.
All control circuits from a source outside of this panel
are to be #14 AWG Orange.
• All control circuit neutrals from a source outside of
this panel are to be no smaller than #14 AWG White/
Orange Tracer.
All analog inputs are to be connected with shielded
cable. Shield terminated at panel side and isolated at
device side.
All shielding is to be grounded at a single point on the
chassis.
Analog wiring must be run separate from AC wiring
and kept separate within the enclosure.
All analog signal wiring shall be grounded at one end
only. Ground shield of signal cables.
Use alpha P/N 2423C, 3 Cond, 18 AWG, shielded or
approved equal.
Only one customer network cable to switch.
• Unused de ned as having a previous assignment.
Spare de ned as no previous assignment.
Where applicable, remove jumper between connec-
tions if used.
All power circuits from a source outside of this panel
are to be no smaller than #12 AWG Orange.
All power circuit neutrals from a source outside of
this panel are to be no smaller than #12 AWG White/
Orange Tracer.
All equipment grounds must be Green/Yellow. For
ground conductors larger than #6 AWG, apply Green/
Yellow heat shrink or color conductor with marker at
both ends.
All power sources for heating devices shall be sup-
plied by others.
Designated for a trip function (i.e. limit trip, se-
quence shutdown, etc.). Recommended hard wire
connection.
Use alpha P/N 2422C, 2 Cond, 18 AWG, shielded or
approved equal.
Category 6 Ethernet cable is recommended for all of
our equipment.
SEPARATION OF INTRINSICALLY SAFE CIRCUITS (IF
USED)
The intrinsically safe wiring enters on the bottom-left
wall of the PLC control enclosure.
To reduce the possibility of interconnection, additional
requirements exist for the separation of intrinsically safe
and non-intrinsically safe circuits. Exceptions to this rule
may be found in NEC Section 504-30(A)(1) and (2).
Separation by distance:
The distance between intrinsically safe eld wiring
terminals and non-intrinsically safe eld wiring termi-
nals shall be a minimum 8 inches.
The distance between intrinsically safe eld wiring
terminals and non-intrinsically safe eld circuits shall
be a minimum 5 inches.
The distance between intrinsically safe eld wiring
terminals and non-intrinsically safe eld circuits and
wiring shall be a minimum 5 inches.
The distance between intrinsically safe eld wiring
terminals and non-intrinsically safe internal wiring
shall be a minimum 2 inches.
Wiring Requirements