7 – 3
Section 7 • Compressor Control Setpoints
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
CAPACITY SLIDE VALVE
Load/Unload Interval time: This is the cycle time be-
tween making capacity slide position adjustments.
Max Load/Unload Adjustment per interval: This is the
maximum amount the capacity position command
may be adjusted by every time through the Load/
Unload Cycle timer.
AUTO START/STOP
Auto Start Pressure: When suction pressure is above
this setpoint for the Auto Start Delay Time, the com-
pressor will be commanded to start.
Auto Stop Pressure: When suction pressure is below
this setpoint and capacity slide position is below
Minimum Slide Position for the Auto Stop Delay time,
the compressor will be commanded to stop.
Auto Start Delay: Amount of time Auto Start pres-
sure must be met before the compressor will be com-
manded to start.
Auto Stop Delay: Amount of time Auto Stop pressure
must be met before the compressor will be com-
manded to stop.
• Minimum Slide Position: Slide position must be be-
low this setpoint (indicating the compressor is fully
unloaded) before the compressor will be command-
ed to stop.
MAIN MOTOR VFD
Max Speed Increase/Decrease per interval: This is the
maximum amount the main motor speed command
may be adjusted by every time through the Load/
Unload Cycle timer.
Forced Unload Rate: If a forced unload condition ex-
ists and the main motor is running above 50% speed,
this is the rate it will decelerate until it reaches 50%
speed and the capacity slide begins unloading.
Compressor Control Setpoints Screen 1 - Process Temperature
The Compressor Control Setpoints page 1 (Process
Temperature) screen appears when navigating to
“Compressor Control Setpoints” from the menu
screen when Process Temperature control is selected.
Setpoints for desired process temperature, capacity
slide valve control, auto start-stop, and main motor VFD
are settable within this screen. For more information
and operational descriptions, see section 2 “Operational
Descriptions.
The following groups of setpoints are settable. If mul-
tiple groups of setpoints are being used, the active
group of setpoints is designated by the “Setpoint 1” or
“Setpoint 2” text being shown in green. Auto Start/Stop
and Main Motor VFD Setpoints will appear if selected.
PROCESS TEMPERATURE CONTROL
Target Process Temperature: This is the desired pro-
cess temperature the compressor will try to maintain.
Upper and Lower Deadband: This is a range of tem-
peratures above and below the Target Process
Temperature. Within this range, no capacity slide
position adjustments will be made.
Upper and Lower Proportional Band: This is a range
of temperatures above and below the Target Process
Temperature. Within this range, the controller will
make proportionally smaller adjustments to capacity
slide position.
CAPACITY SLIDE VALVE
Load/Unload Interval time: This is the cycle time be-
tween making capacity slide position adjustments.
Max Load/Unload Adjustment per interval: This is the
maximum amount the capacity position command
may be adjusted by every time through the Load/
Unload Cycle timer.
AUTO START/STOP
Auto Start Temperature: When process temperature
is above this setpoint for the Auto Start Delay Time,
the compressor will be commanded to start.
Auto Stop Temperature: When process temperature
is below this setpoint and capacity slide position
is below Minimum Slide Position for the Auto Stop
Delay time, the compressor will be commanded to
stop.
Auto Start Delay: Amount of time Auto Start tem-
perature must be met before the compressor will be
commanded to start.
Auto Stop Delay: Amount of time Auto Stop tempera-
ture must be met before the compressor will be com-
manded to stop.
• Minimum Slide Position: Slide position must be be-
low this setpoint (indicating the compressor is fully
unloaded) before the compressor will be command-
ed to stop.