Section 11 • Alarms, Trips, Status Information & Troubleshooting
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Alarm Message Cause(s) Notes
(A080) Alarm: User De ned Alarm 2 Message De ned in "Device Names"
Screens
(A081) Alarm: User De ned Alarm 3 Message De ned in "Device Names"
Screens
(A082) Alarm: User de ned Alarm 4 Message De ned in "Device Names"
Screens
(A083) Alarm: User de ned Alarm 5 Message De ned in "Device Names"
Screens
(A084) Alarm: (Unassigned)
(A085) Alarm: (Unassigned)
(A086) Alarm: (Unassigned)
(A087) Alarm: (Unassigned)
(A088) Alarm: (Unassigned)
(A089) Alarm: Oil Cooler Fan VFD
Fault
Fault Contact open on Oil Cooler
VFD
If controlling a VFD Type Oil Cooler
(A090) Alarm: Oil Cooler Fan (Step
Type) Starter Fault
Oil Cooler Fan commanded to start,
running con rmation not received.
If controlling a Step Type Oil Cooler
(A091) Alarm: (Unassigned)
(A092) Alarm: (Unassigned)
(A093) Alarm: Aftercooler 1 Fan VFD
Fault
Fault Contact open on Aftercooler 1
VFD
If controlling a VFD Type Aftercooler
1
(A094) Alarm: Aftercooler 1 Fan
(Step Type) Starter Fault
Aftercooler 1 Fan commanded to
start, running con rmation not
received.
If controlling a Step Type Aftercooler
1
(A095) Alarm: Aftercooler 2 Fan VFD
Fault
Fault Contact open on Aftercooler 2
VFD
If controlling a VFD Type Aftercooler
2
(A096) Alarm: Aftercooler 2 Fan
(Step Type) Starter Fault
Aftercooler 2 Fan commanded to
start, running con rmation not
received.
If controlling a Step Type Aftercooler
2
(A097) Alarm: Economizer High
Level
Economizer High Liquid Level Switch
Activated
If monitoring the liquid level in
economizer vessel
(A098) Alarm: Chiller High Level Chiller High Liquid Level Switch
Activated
If monitoring the liquid level in
chiller vessel
(A099) Alarm: Air Cooled Condenser
Fan VFD Fault
Fault Contact open on Condenser 1
VFD
If controlling a VFD Type Condenser
(A100) Alarm: Air Cooled Condenser
(Step Type) Starter Fault
Condenser Fan commanded to start,
run con rmation not received.
If controlling a Step Type Condenser
(A101) Alarm: Unassigned
(A102) Alarm: Unassigned
(A103) Alarm: (Unassigned)
(A104) Alarm: (Unassigned)
(A105) Alarm: (Unassigned)