Section 11 • Alarms, Trips, Status Information & Troubleshooting
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Trip Message Cause(s) Notes
(T108) Trip: Smoke Detector Tripped Smoke Detector Trip Contact
opened, detected smoke in com-
pressor enclosure
If compressor is in an enclosure
(T109) Trip: (Unassigned)
(T110) Trip: High Enclosure
Temperature
Temperature inside Enclosure ex-
ceeds Enclosure Temperature - High
Trip Setpoint
If compressor is in an enclosure
(T111) Trip: Out of Range: 4-20 mA
Caphold Target
4-20mA Caphold Input is
Disconnected or Raw Value is less
than 3.5 mA or greater than 20 mA
If remote manual mode active and
4-20mA caphold selected as Remote
Manual Source
(T112) Trip: Out of Range: Building
Temperature
Building Temperature RTD Input is
Disconnected or Raw Value is less
than 3.5 mA or greater than 20 mA
(If using 4-20mA Transmitter)
If compressor is in an enclosure
(T113) Trip: Out of Range: Methane
Detector
Methane Detector is Disconnected
or Raw Value is less than 3.5 mA or
greater than 20 mA
If compressor is in an enclosure
(T114) Trip: Out of Range: EPCS Low
Pressure
Low Side EPCS Relief Instrument is
Disconnected or Raw Value is less
than 3.5 mA or greater than 20 mA
Active if EPCS Safety Selected.
(T115) Trip: Out of Range: EPCS High
Pressure
High Side EPCS Relief Instrument is
Disconnected or Raw Value is less
than 3.5 mA or greater than 20 mA
Active if EPCS Safety Selected.
(T116) Trip: Out of Range: Motor
Vibration 1
Motor Vibration 1 Instrument is
Disconnected or Raw Value is less
than 3.5 mA or greater than 20 mA
If Motor Vibration Sensor 1 is
installed
(T117) Trip: Out of Range: Motor
Vibration 2
Motor Vibration 2 Instrument is
Disconnected or Raw Value is less
than 3.5 mA or greater than 20 mA
If Motor Vibration Sensor 2 is
installed
(T118) Trip: Out of Range:
Compressor Vibration 1
Compressor Vibration 1 Instrument
is Disconnected or Raw Value is less
than 3.5 mA or greater than 20 mA
If Compressor Vibration Sensor 1 is
installed
(T119) Trip: Out of Range:
Compressor Vibration 2
Compressor Vibration 2 Instrument
is Disconnected or Raw Value is less
than 3.5 mA or greater than 20 mA
If Compressor Vibration Sensor 2 is
installed
(T120) Trip: (Unassigned)
(T121) Trip: (Unassigned)
(T122) Trip: (Unassigned)
(T123) Trip: (Unassigned)
(T124) Trip: (Unassigned)
(T125) Trip: (Unassigned)
(T126) Trip: (Unassigned)
(T127) Trip: (Unassigned)
(T128) Trip: (Unassigned)