Page view 125
11 – 12
Section 11 • Alarms, Trips, Status Information & Troubleshooting
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Trip Message Cause(s) Notes
(T039) Trip: Out of Range: Main
Motor Amps
Main Motor Current Transmitter is
Disconnected or Raw value is less
than 3.5 mA or Greater than 20.5
mA.
(T040) Trip: Out of Range: Capacity
Slide Position
Capacity Slide Cable is Disconnected
or Raw value is less than 0 mV or
Greater than 5200 mV.
(T041) Trip: Out of Range: Volume
Slide Position
Volume Slide Cable is Disconnected
or Raw value is less than 0 mV or
Greater than 5200 mV.
(T042) Trip: Out of Range: Process
Temp
Process Temperature Instrument is
Disconnected or Raw value is less
than 3.5 mA or Greater than 20.5
mA (if using a 4-20mA Temperature
Transmitter).
(T043) Trip: Out of Range: Motor
RTD Phase A
Winding RTD is disconnected or
faulty
(T044) Trip: Out of Range: Motor
RTD Phase B
Winding RTD is disconnected or
faulty
(T045) Trip: Out of Range: Motor
RTD Phase C
Winding RTD is disconnected or
faulty
(T046) Trip: Out of Range: Motor
RTD ODE
Bearing RTD is disconnected or
faulty
(T047) Trip: Out of Range: Motor
RTD DE
Bearing RTD is disconnected or
faulty
(T048) Trip: High Motor Phase A
Temperature
Phase A Motor Winding Temperature
exceeds Motor Winding
Temperature High Trip Setpoint
Active if Displaying Motor Winding
Temperatures
(T049) Trip: High Motor Phase B
Temperature
Phase B Motor Winding Temperature
exceeds Motor Winding
Temperature High Trip Setpoint
Active if Displaying Motor Winding
Temperatures
(T050) Trip: High Motor Phase C
Temperature
Phase C Motor Winding Temperature
exceeds Motor Winding
Temperature High Trip Setpoint
Active if Displaying Motor Winding
Temperatures
(T051) Trip: High Motor DE Bearing
Temperature
Drive End Motor Bearing
Temperature exceeds Motor Bearing
Temperature High Trip Setpoint
Active if Displaying Motor Bearing
Temperatures
(T052) Trip: High Motor ODE Bearing
Temperature
Opposite Drive End Motor Bearing
Temperature exceeds Motor Bearing
Temperature High Trip Setpoint
Active if Displaying Motor Bearing
Temperatures
(T053) Trip: High Motor Vibration -
Sensor 1
Motor Vibration exceeds Motor
Vibration High Trip Setpoint (Sensor
1)
Active if Displaying Motor Vibration
Sensor 1