Single Screw Compressor PLC Operation Manual •Vilter/Emerson • 35391CM
Section 1 • General Information
All wiring to and from the Variable Frequency Drive
(VFD) starter shall conform to the National Fire
Protetcion Association 70 (NFPA-70), local codes and
the manufacturer’s guidelines and speci cations.
Thoroughly read the manufacturer’s VFD installation
and instruction manuals.
In the event of a code and manufacturer recom-
mendation con ict, always use the more stringent
standard.
Only use an inverter duty rated motor built to NEMA
MG1 PART 30 & 31.
Always used copper conductors to feed the VFD
starter and motor. Use cable with thermoset insula-
tion such as XLPE or XHHW-2 from the VFD to motor.
It is preferred to use VFD cable, service wire company
or equal, between the VFD and the motor per manu-
facturer’s instructions.
It is preferred to use continuous metal conduit to the
VFD starter to the motor.
If non-metallic conduit is used, VFD cable must be
used.
• If using VFD cable in metal conduit, the metal con-
duit must be insulated at the motor, so that the metal
conduit is not a continuous run.
• Always use exible metallic liquid-tight conduit to
feed the motor from metallic conduit.
Grounding conductor must run from the VFD ground
terminals directly to the motor conduit box. Always
use proper grounding techniques (Star Method) and
sized according to the NFPA 70 NEC.
Always use bonding bushings on all conduit ends,
Always use bonding bushings on all conduit ends,
with proper size braided copper cable bonded to the
starter panel.
All grounding and bonding conductors and lugs must
terminate on bare metal and not to painted surfaces.
Always use a minimum of 3% impedance line reactor
such as MTE or equal.
Where the cables to the motor are longer than 50’,
always use a load reactor (customer must provide
Vilter with cable lengths from feeder to starter and
from starter to motor).
Where the cables to the motor are longer than 500’,
always use a DV/DT load lter (customer must pro-
vide Vilter with cable lengths from feeder to starter
and from starter to motor).
Where the cables to the motor are longer than 1000’,
always use a sine lter (customer must provide Vilter
with cable lengths from feeder to starter and from
starter to motor).
Line and load conductors must be separated, as
much as the starter cabinet will allow, and cannot be
in the same conduit or cable chase.
By no means shall power and control cables run in
parallel - cables must be separated, as much as the
starter cabinet will allow, and cannot be in the same
conduit or cable chase.
For analog signals, use twisted shielded control cable
rated for 600V.
When a generator is feeding a VFD starter, use a 5%
line reactor.
Some countries require RFI/EMI lters -- please con-
sult country codes and standards.
As an insurance policy against motor shaft currents,
use a split ring bearing protection ring on the motor
shaft with the non-load bearing insulated.