Service Menu Parameters
135 Liebert
®
iCOM
®
S511 Cascaded Units Min Run—Sets a minimum run time after a commanded unit is turned On.
The timer must expire before the unit can go back into standby. This parameter range is 2-360
minutes. The factory default is 30 minutes.
S512 Cascaded Units Control Delay
Teamwork Mode 1: Mode C: once the unit was started, the fanspeed control will start
immediately, but the cooling / humidity control will be delayed by the value set in S512 Cascaded
Units Control Delay. Mode B: the S512 timer is ignored; a cascaded unit starts control w/ no
delay.
Teamwork Mode 3: All Modes: When the cascaded standby unit was started, the normal unit
control is delayed by the value set in S512 Cascaded Units Control Delay. During this delay time,
the fanspeed control and the cooling control uses the shared System values (based on AVG or
MAX); heat, hum and dehumidification is disabled When the S512 timer has elapsed, the unit
transitions to normal unit control, which is depending on the operating mode. This parameter
range is 0-30 minutes. The factory default is 5 minutes.
S513 Start all Standby Units by HT—Activates all units to cool when a High Temperature Alarm
occurs.