Operation
23 Liebert
®
iCOM
®
Setting the counter to 0 will auto-reset the alarm without the need of pressing the reset button on the
display. Even if the pressure in the system drops below the alarm point, the compressor will remain
Off until the system is reset.
Digital Scroll High Temperature
A protective maximum operating compressor temperature limit is imposed on units with digital scroll
compressor(s) with thermistor. If the digital scroll temperature reaches the maximum temperature
threshold, the compressor will be locked out for at least 30 minutes and an alarm will be annunciated.
If after 30 minutes the temperature has cooled to a safe operating temperature, the compressor will
resume operation.
Each time a high-temperature alarm occurs, HT 1 Alarm Counter (Service Menu, Diagnostics) or
HT 2 Alarm Counter (Service Menu, Diagnostics) is increased by one. Once these counters reach five
occurrences in a rolling four-hour period, the compressor will be locked out. The alarm can be reset
once the temperature returns to a safe level by:
1. Setting the counter back to 0 from the display and pressing the alarm reset button.
2. Shutting Off power to the control board by turning the cooling unit's main power disconnect
switch Off and On.
3.1.4 Compressor Timing—Short-Cycle Protection
To help maximize the life of your compressor(s), there is a start-to-next start delay for each single
compressor.
3.1.5 Compressor Sequencing on Two-Compressor Units
Compressor Sequencing parameter (Service Menu, Options Setup) is intended to maintain equal run
times between compressors. This setting has three selection possibilities:
Always use Compressor 1 as lead compressor.
Always use Compressor 2 as lead compressor.
•Auto:
First priority: if the safety timings are acceptable for only one compressor, then it is the next
to be started/stopped.
If both compressors are Off: the one with fewer working hours is the next to start.
If both compressors are in operation: the one that has been operating longer since the last
start is the next to be stopped.
NOTE
If the unit is equipped with manual reset high head pressure switches, or if the auto reset high
head pressure switches don’t reset, the compressor will not be turned back on, but there will be
a 30-second delay from when the high head pressure situation occurs and when the alarm is
annunciated.
NOTE
This delay may cause a short cycle if there is a very light room load. A short cycle means that
the compressor has cycled On and Off 10 times in the past hour. This is typically caused by a
lack of load or control settings set too tight (see 3.7 - Control Types for more information on
the control adjustment). Should short cycling still occur after the control has been adjusted,
contact technical support at 800-543-2778 to adjust the minimum compressor Off delay.
NOTE
The Auto setting attempts to maintain equal run times between compressors. However,
the control will not turn Off a compressor to equalize run time when it is needed to
control the space.