Operation
61 Liebert
®
iCOM
®
When supply air compensation has been invoked, it will be indicated on the unit view by a small
downward-pointing arrow. See Figure 53.
Figure 53 Supply Compensation in Unit View
During normal operation, as the rack temperature increases above the fan temperature setpoint, the
fan speed will increase until it reaches 100% speed. 100% fan speed is achieved once the controlling
temperature reaches a value equal to 100% of the fan control band, or S116 Fan Setpoint + 1/2(S150
Fan Deadband) + 1/2(S149 Fan Temp Prop Band).
How many degrees the supply temperature will be lowered while supply compensation is invoked
depends on how many degrees the fan controlling temperature has exceeded the control band
compared to S116 Supply Compensation Value.
Example: With a Fan Setpoint of 70ºF and Proportional band of 10ºF, 0ºF deadband, the fan
speed is 100% when the rack temperature is 75ºF. If S116 Supply Compensation value = 10ºF, the
supply air temperature will lower one degree for every degree the rack temperature increases
outside the fan control band. This means if the air temperature setpoint is 65ºF, and the rack
temperature increase to 77ºF, the supply air temperature will lower to 63ºF.
Supply
Compensation
in Unit View