Emerson Liebert iCOM User Manual Page 134

  • Download
  • Add to my manuals
  • Print
  • Page
    / 192
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 133
Service Menu Parameters
Liebert
®
iCOM
®
124
Figure 105 Setpoints screen, page 2 of 9
S113 Enable Temp Compensation—Temperature compensation allows for a second or even a third
sensor to be used that will influence the units cooling or heating. Return compensation can be used
when the supply or remote sensors are being used for control. Then the return sensor is then
monitored to maintain a minimum return temperature.
Supply compensation can be used only when Optimized Aisle is enabled. The supply sensor will not
only be used for controlling cooling capacity but will also monitor the cold aisle temp to ensure that
the cold aisle temperature setpoint is met.
S114 Return Compensation Setpoint—The temperature setpoint where compensation begins to
operate by increasing the supply air setpoint.
S115 Return Compensation Band/Value—The return compensation band / value will determine
how quickly the cooling capacity is adjusted as the return temperature drops below the return
compensation setpoint.
S116 Supply Compensation Value—The Supply Compensation value determines how much the
supply temperature setpoint will be reduced when the units fan speed is at 100% and the cold aisle is
not able to maintain temperature setpoint.
Any modifications to the supply temperature setpoint will be shown at the temperature setpoint on
parameter S103 as the actual active control point.
S118 Comp Cap Filter at 0-100%—Controls the rate of change during comp load changes to avoid
overshoots. The filter value depends on the current control deviation from the setpoint.
On the setpoint (at 0%), it’s typically set lower (slow), and at the end of the P-band (at 100%) it’s
typically set higher (faster). The value is given in % control output change per second.
S119 Capacity Transition Filter—This parameter should only be adjusted by a factory-service
trained technician. The transition capacity filter controls how quickly the capacity changes between
different modes of operation.
This filter helps with the transition to avoid overshoot.
S120 CW Cap Filter at 0 - 100%— The CW Filter at 0% / 100% Controls the rate of change during a
valve position adjustment to avoid overshoots. The filter value depends on the current control
deviation from the setpoint. On the setpoint (at 0%), it’s typically set lower (slow), and at the end of
the P-band (at 100%) it’s typically set higher (faster). The value is given in % control output change
per second.
S121 BMS Backup Temp Setpoint—Selects a temperature setpoint that will be activated in the
event of a BMS Timeout. The BMS timer must be configured for this parameter to activate.
S122 2nd Temperature Setpoint—Selects a temperature setpoint that will be activated in the
event of a customer input signal configured as the second setpoint. The customer input must be
configured for this parameter to activate.
Page view 133
1 2 ... 129 130 131 132 133 134 135 136 137 138 139 ... 191 192

Comments to this Manuals

No comments