Operation
71 Liebert
®
iCOM
®
3.10.3 Analog Inputs—Liebert CW
and Liebert DS
Air-Cooled Units
The Liebert iCOM allows an external sensor or analog device to be connected, scaled and viewed on
the Liebert iCOM large display for Liebert CW and Liebert DS air-cooled units only. These external
devices require optional analog input connections that can be installed on new units at the factory or
added to existing units in the field. The option provides the electrical connection from the Liebert
iCOM control board to the required factory-supplied plug, harness and terminal strip. For parts,
contact Liebert Services at (800) 800-543-2778. If a Liebert CW or Liebert DS air-cooled unit is
equipped with this option, then a 0-10VDC, 0-5VDC or a device such as a sensor or a damper can be
connected to terminals 41 and 42, 43 and 44, 45 and 46 or 47 and 48. See Table 11 for analog input
availability.
Follow the settings illustrated in Figure 62 and Table 12 to set the input type based on the sensor
output being used. The default analog input is 0-5VDC. Only properly trained and qualified service
technicians should change the analog input type.
Figure 62 Analog connection control board switch
Table 11 Number of analog inputs
Unit Type
Number of Analog Inputs
Liebert CW with MBV 4
Liebert CW with 3P (Stem Valve) 3; one used for valve feedback
Liebert DS Air-Cooled (DX) 2; two used for suction pressure management
NOTE
This option is not available on fluid-cooled units. Fluid-cooled units use all four
analog inputs for low and high refrigerant pressure management.
NOTE
The analog inputs must be configured with the large display. The small display
can only view them.
Table 12 Analog connection control board switch position
Analog Input # Input #1 Input #2 Input #3 Input #4
Control Board Switch Number 1 2 3 4 5 6 7 8
Analog Input Device Value
0 to 10VDC Off Off Off Off Off Off Off Off
0 to 5VDC On Off On Off On Off On Off
Switches #9 and #10 not applicable to Liebert CW or to Liebert DS.
On
Off
Switch Position
Switches #9 and #10 not
applicable to Liebert CW
or to Liebert DS