User Menu Parameters
Liebert
®
iCOM
®
114
Figure 96 Sensor data screen, page 3
U325 Remote Sensor 1/2—Displays the actual remote sensor reading for each remote sensor. The
actual value reported here is dependent on how the sensor is setup. If the sensor is set to average,
then an average of the 2 temperature readings per sensor will be shown. If the sensor is set to
maximum, then the maximum value will be shown.
U326 Remote Sensor 3/4—Same as Remote Sensor 1/2
U327 Remote Sensor 5/6—Same as Remote Sensor 1/2
U328 Remote Sensor 7/8—Same as Remote Sensor 1/2
U329 Remote Sensor 9/10—Same as Remote Sensor 1/2
U331 Rem Sensor Control is set to:—Shows if the sensors are set to be averaged or maximum.
This value can be changed in the service menu under remote sensors.
U331 # of Remote Control Sensors—Shows the number of connected remote control sensors.
U332 Remote Sensor Unit Average—Shows the remote sensor unit average. This value is
displayed regardless of how the unit is setup for control purposes.
U333 Remote Sensor Unit Maximum—Shows the remote sensor unit maximum. This value is
displayed regardless of how the unit is setup for control purposes.
U334 Remote Sensor System Average—Shows the “SYSTEM” remote sensor average. This value
is displayed regardless of how the unit is setup for control purposes.
U336 Remote Sensor System Maximum—Shows the “SYSTEM” remote sensor maximum. This
value is displayed regardless of how the unit is setup for control purposes.