Emerson Liebert iCOM User Manual Page 66

  • Download
  • Add to my manuals
  • Print
  • Page
    / 192
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 65
Operation
Liebert
®
iCOM
®
56
3.8 Supply Control
The supply temperature sensor should be placed in an area that is influenced only by the unit it is
connected to.
The Supply Air sensor can be used to control or reference the discharge air temperature of the cooling
unit. This sensor can be added to existing Liebert iCOMs by purchasing the supply sensor and wiring
harness. The supply air sensor must be connected to P13 pins 1 & 2. Contact your local Emerson
representative for pricing and installation.
When the supply sensor is set to Control, the unit will control the amount of cooling / heating
being provided based on maintaining the discharge air temperature. The return air sensor may
still be used to control fan, humidity or as temperature/humidity reference of the room.
Supply Limit: Chilled water units may be set up with the supply air sensor to maintain a
minimum air temperature under a raised floor to help prevent condensation. To avoid supply
temperatures that are too low, the Supply Limit can influence the opening of three-point or
analog actuators or the output of analog valves. The control compares the deviation from the
return air setpoint and the supply limit setpoint and calculates the output to the actuator from
the smaller deviation.
When the supply air sensor is set up for Temperature control, additional Supply Air configuration
parameters (valve pulse, cooling filters and return compensation) can be used to further enhance
the supply air control.
The valve pulse and cooling filter timer can be adjusted to prevent oscillating around the supply
setpoint and still allow for rapid valve adjustments to compensate for heat load changes. Contact
your local Liebert service personnel for adjustments.
Return Compensation begins to increase the supply air setpoint when the return air decreases
below the return air setpoint.
Example
Setting the return compensation value in the Service, Setpoints menu to 5°F (2.7°C) will
increase the supply setpoint from 50°F to 55°F (10°C to12.8°C) when the return temperature is
at the low limit of the proportional band.
NOTE
On units equipped with a 3P actuator type valve, response can be improved bu using the
feedback signal. Feedback is not required for supply air control and is not available on units
with fluid economizer. See 3.2.3 - Chilled Water Control.
NOTE
Supply control and limit are calculated on each unit, independent of the other sensor readings
on the network.
Page view 65
1 2 ... 61 62 63 64 65 66 67 68 69 70 71 ... 191 192

Comments to this Manuals

No comments