3.4.2 Liebert Air Economizer
System Overview
Controller settings will vary depending on the application. The objective of all settings is the same: to
expel warm air from the conditioned space and bring in cooler air through the Liebert Air
Economizer. This function is monitored continuously by the Liebert iCOM that controls the Liebert
Air Economizer.
Figure 34 shows an example of the air flow pattern of a Liebert Air Economizer system. The indoor
sensor must be positioned where there is airflow when the system is in full economizer operation and
when the system is operating in non-economizer mode.
If the indoor damper position has been changed to 0% from the factory default of 15%, then the indoor
sensor must be moved, preferably to the hot aisle.
Figure 34 Air flow pattern of a Liebert Air Economizer system-regular ceiling
Mixing
Box
Outdoor
Temperature /Humidity
Sensor
Outdoor
Damper
Indoor
Temperature/Humidity
Sensor
Roof
CRAC
Supply Sensor
5-15ft. (1.5 to 4.5m)
from cooling unit
Pressure Relief
Vent
(Not by Emerson)
Return
Room Air
Equipment
Rack
Cold
Aisle
Hot
Aisle
Hot
Aisle
Front
of Unit
Liebert Air
Economizer
Equipment
Rack
Liebert iCOM
Indoor
Damper
Outside Air
Duct