Return + Supply Compensation: This selection provides the ability to enable both supply and
return compensation settings as described above.
Figure 54 Supply/return compensation
Figure 55 Temperature/humidity/static pressure control sensors in Optimized Aisle
76 78
74
7372
100%
Compensation
50%
Compensation
Blower at 100%
of Capacity
Blower Proportional Band
Fan Speed Proportional
Band 8°F (4°C)
Supply Temperature Setpoint
will be decreased by the Supply
Compensation band when the
fan speed proportional band
has doubled
After the blower reaches 100
percent and the temperature
continues to increase, the
supply temperature setpoint will
be decreased proportionally
Supply
Compensation
Band 8°F (4°C)
Return
Temperature/
Humidity
Sensor
Supply Temperature
Sensor
Inlet Rack Sensor
Static Pressure