Service Menu Parameters
161 Liebert
®
iCOM
®
Figure 150 Sensor calibration/setup screen, page 7 of 7
S670 SP Transducer is Connected to—Sets the analog output that will be used for the static
pressure transducer. This parameter is selectable from None, Ana In 1, Ana In 2, Ana In 3 and Ana In
4. The factory default is none.
S671 SP Transducer Setup in—Sets the unit of measure that will be used for the static pressure
transducer. This parameter is selectable in inWC or PA. The factory default is PA.
S672 SP Transducer Low—Sets the unit of measure that will be used for the low static pressure
transducer. This parameter is selectable from 0-9.999 inWC. The factory default is 0.000 inWC.
S673 SP Transducer High—Sets the unit of measure that will be used for the high static pressure
transducer. This parameter is selectable from 0-9.999 inWC. The factory default is 2.005 inWC.
S677 Results:—Read-only string that describes S678 through S681.
S678 SP Transducer Low—Shows the status of the low static pressure transducer in both inWC
and Pa after it’s setup at S672.
S679 SP Transducer High—Shows the status of the high static pressure transducer in both inWC
and Pa after it’s setup at S673.
S680 Actual SP Signal—Shows the actual static pressure transducer percentage.
S681 Current Static Pressure—Shows the current static pressure based on low and high settings.