Service Menu Parameters
Liebert
®
iCOM
®
172
Figure 161 Options setup, page 4 of 6
S435 Measure Type—Determines the measurement units and range for each analog input.
Factory Std measurement type means the input is being used by the factory-configured device
for unit control and cannot be set to any other measurement type.
Not Config measurement type means the input is available for custom sensor use, but has not
been configured. After unit code execution, all analog inputs that are available will be set to “Not
Config,” and can then be set to any of the following choices by the user:
Air Pres 1, 2, 3 or 4
Pressure 1, 2, 3 or 4
Temp 1, 2, 3 or 4
Percent 1, 2, 3 or 4
It is not necessary to match a measurement type number to the analog input number (i.e., “Air
Pres 2” does not have to be connected to Analog Input 2). The numeric designation on each
measurement type is just to allow the user to differentiate between readouts if multiple
measurements of the same type are required.
Precision—Parameters in the Precision column must match the DIP switch settings for each analog
input being used. There are two choices for these parameters: 0-5V and 0-10V. This setting will also
regulate the range of an analog input’s linear characteristic on Page 5 of the Options Setup screen of
the Service Menu (see Figure 162).
S441 Units system for Custom Inputs—Determines the unit type (English or SI) that will be used
for the setup and readout of custom sensors. This parameter affects only analog inputs. All lines in
other menus involving pressures or temperatures will have their readout type determined by line
U404 of the User - Selection menu. The table below shows the English and SI units for each
measurement type.
When the unit type is changed on line S441, the linear characteristics for all of the inputs on Page 5 of
the Options Setup screen of the Service Menu will be converted to match the new units system, and
the readout in the Sensor Data in the User Menu will also change to reflect the new units.
Measurement
Type
Units
English SI
Air Pres inWC Pa
Pressure PSI Bar
Temp °F °C
Percent % %