Service Menu Parameters
133 Liebert
®
iCOM
®
S198 SP Sensors in Avg for TW—Sets the number of sensors used when averaging sensors in the
team work. This parameter is selectable from 1-32. The factory default is 2.
S199 - Operation @ Sensor Failure—This parameter determines what action to take if the static
pressure sensor fails (non-teamwork). There are two options to use when handling a static pressure
sensor failure, they are SP OFF = static pressure control Off, where the control will use S146 to
control the fan when the sensor is lost or Freeze Speed = keep the fanspeed unchanged based on the
last reading to iCOM. Things that need to override fanspeed such as freeze protection can still change
the fanspeed.
S19A SP Upper Range—The control calculates the Upper Range by using S191 “SP Setpoint” and
S192 “SP Deadband,” the results on lines show both values, in WC and Pa.
S19B SP Lower Range—The control calculates the Lower Range by using S191 “SP Setpoint” and
S192 “SP Deadband,” the results on lines show both values, in WC and Pa.
Service—Unit Diary Menu Screens (Large Display Only)
Unit Diary—Shows all entered program changes and maintenance performed on the unit. The Unit
Diary serves as a note pad, where information can be added through the Liebert iCOM Service Tool.