Operation
29 Liebert
®
iCOM
®
Figure 27 DIP switch locations on Liebert iCOM control board
6. P68 must have a jumper placed between the top and bottom two pins on the left side and one
placed between the top and bottom pins on the right side, the two middle pins should be left
unconnected.
7. Go to Service/Diagnostics Service Menu and find S379. Set this option to Feedback and note that
S380 will go to Yes and S381 will go to Ongoing. If Feedback is already selected, then go to line
S380 and manually select Yes. This means that the Liebert iCOM is doing auto calibration on the
valve using the feedback now available through the potentiometer. Wait for S381 to say Idle and
then the process is complete.
Chilled water units that contain a motorized ball valves) are connected to the control by an analog
output. The analog output is driven proportionally to the call for cooling as shown in Figure 28.
Larger chill water units may contain two motorized ball valves in which both valves are controlled in
parallel for cooling. The two valves may be set to Cascade mode for dehumidifying to minimize the
overcooling effect during dehumidification.
8. Turn the unit On at the Liebert iCOM.
Figure 28 Chilled water valve control (example: cooling)
NOTE
Depending on the valve specifications, the voltage output may be a 0-10VDC or a 2-10VDC that
is scaled automatically within the control.
+ 100%
Cooling
Cooling
½ Proportional Band
0% - Closed
Requested Position
100% Fully Open
0%
Setpoint
+ Temp