Service Menu Parameters
127 Liebert
®
iCOM
®
S138 DT2 (Room/FC Fluid) Value—Sets the delta between the actual temperature and fluid
temperature that must be met before free-cooling will occur.
Example: Actual Temperature = 75°F
Free-cooling Temperature = 70°F
DT2 Value = 4
Since the difference between the free-cooling fluid and the actual temperature is 5°F and the DT2
value is set to 4°F, then free-cooling would be utilized.
S139 Minimum CW Temp—Enables the temperature at which free-cooling can operate
independently without assistance of the compressor circuit(s).
S140 Minimum CW Temp Value—Sets the water temperature at which 100% free-cooling can be
provided to handle the full room load. When the fluid temperature is below this setting, then the
compressors will no longer turn On until the water temperature is above the minimum CW Temp.
S141 Lockout FC at FC Fluid below—Prevents frost from building up on the free-cooling pipes
when the outdoor ambient is extremely low by turning Off the free-cooling circuit when the water
temperature is too low.
Figure 108 Setpoints screen, page 5 of 9
S146 Fan Control Sensor—Controls the fan speed for modulation. Options for this setting are
Supply, Return, Remote, and Manual Mode.
If manual mode is selected, then the fan speed can be controlled from the local display or through a
building management system.
S147 Fan Setpoint—Activated when a temperature sensor is being used to control the fan speed. If
the same sensor is used for temperature control and fan speed control, then this value will reflect the
same setpoint as the temperature control setpoint. Manual mode uses the Fan Speed STD for control.
S148 Fan Temp Control Type—Sets the type of control the unit will use to control fan speed.
PI controls gain is set in the Temp Prop / Integral parameter.
PI control will operate the fan speed so that the actual temperature of the fan control sensor is
equal to the fan temp setpoint. If proportional only is selected, the fan will change “ONLY” based
on the deviation from setpoint which will allow the actual temp to settle higher than setpoint.