Emerson Liebert iCOM User Manual Page 64

  • Download
  • Add to my manuals
  • Print
  • Page
    / 192
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 63
Operation
Liebert
®
iCOM
®
54
The integration (I) time works with the proportional band in PI Control to stage call for cooling before
the actual temperature increases far above the temperature setpoint. The “I” portion does this by
doubling the current “P” deviation for every time the “I” has elapsed.
Example: If the “P” deviation is 50% within the “I” time (e.g., 5 min), the call for cooling will be
doubled, giving 100% in 5 minutes.
While this happens, the real temperature “P” deviation will decrease. If the “P” deviation drops to
40% and the previously calculated “I” was already on 55%, it will shift back to 45% following “P.”
From this point the “I” will continue to calculate the call for cooling, but slower at a slower rate
since the actual room temperature has dropped.
Opening the valves or staging compressor(s) to 62% may decrease the temperature from 40% to
20%, which would drive the “I” down from 62% to 42%.
At this point, “P” is 20% and “I” is 42% (call for cooling, valve opening, compressor[s] stage).
This continues until “P” is 0—on the setpoint or within the deadband.
Setting Up PI control
Generally 3-5 minutes integration time is good for most applications. The proportional band may
depend on the amount of heat load and other factors. Use Table 8 as a guide for making the PI
control settings.
Intelligent—If Intelligent Control is selected, the air temperature/humidity is controlled at or near
the setpoint. The percent temperature/humidity adjustment required is calculated based on logic that
is programmed into the control. This logic simulates the actions that a human would take if manually
controlling the system. This control type is used only on chilled water units.
3.7.2 Humidity Sensor Reading Control Types
The Liebert iCOM has four humidity sensor control types: Dew Point, Relative, Compensated and
Predictive. The humidity sensor adjusts how the Temperature and Humidity Control determines the
percent requirement for humidification/dehumidification. The humidity sensor control type
parameter, Humidity Control Type, is in both the User and Service menus under Setpoints.
Dew Point—The actual return temperature and humidity measured by Liebert iCOM is used
internally to determine the dew point. When dew point control is selected, the user will set the
humidity setpoint in degrees dew point and will also adjust the proportional band in degrees dew
point.
Relative—The actual return air humidity sensor reading is sent to the Temperature and Humidity
Control to determine if and how much humidification/dehumidification is required. The actual return
air humidity reading is displayed on the Status menu. Unnecessary dehumidification can result when
overcooling occurs during a dehumidification cycle. This is because a higher than normal relative
humidity (RH) reading is caused by overcooling the room. This extends the dehumidification cycle.
Later, when the dehumidification ends and the return air temperature rises to the setpoint, the RH
reading falls. The final RH reading will then be lower than actually desired. If significant overcooling
occurred, the RH could be low enough to activate the humidifier.
Table 8 PI control troubleshooting
Problem Solution
Unit is too slow to activate
cooling.
Decrease the proportional band slightly and monitor operation.
Compressor short cycle alarm.
Increase the proportional band slightly and adjust the integration time to 3-5 min.
Monitor compressor run time. Run must be higher than 3 minutes to avoid short
cycle from occurring.
Excessive valve oscillation or
hunting.
Widen the temperature proportional band and/or consider increasing the
integration time.
Page view 63
1 2 ... 59 60 61 62 63 64 65 66 67 68 69 ... 191 192

Comments to this Manuals

No comments