User Menu Parameters
109 Liebert
®
iCOM
®
Figure 91 Set alarms screen, page 2
U213 Supply Sensor Alarms—Enables or disables the supply sensor alarms. When enabled, the
supply temperature and humidity values will be compared to a high and low setting.
U214 High Supply Temperature—Sets the temperature at which the High Supply Temperature
Alarm is activated. This parameter is adjustable from 34°F to 210°F. The factory default setting is
75°F.
U215 Low Supply Temperature—Sets the temperature at which the Low Supply Temperature
Alarm is U21activated. This parameter is adjustable from 34°F to 210°F. The factory default setting
is 50°F.
U219 Remote Sensor Alarms—Enables or disables the Remote sensor alarms. When enabled, the
Remote temperature values will be compared to a high and low setting.
U220 High/Low Remote TemperatureEnables or disables remote air alarm. When enabled, the
high and low temperature alarm will allow a user to adjust the point at which the actual remote
temperature activates a Low Remote Temperature Alarm. This parameter is used when common
alarm points will be shared by all sensors. Otherwise, the remote sensors can be set individually on
page 3. This parameter is adjustable from 34°F to 210°F. The factory default setting 50°F.
U221 Separate thresholds are on page 3—Informational