Emerson 3051S Specifications Page 172

  • Download
  • Add to my manuals
  • Print
  • Page
    / 222
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 171
162
Reference Manual
00809-0100-4001, Rev JA
Appendix A: Reference Data
November 2012
Specifications and reference data
Table A-10. 3051L/3051H pressure transmitter range limits
Table A-11. 3051T gage and absolute pressure transmitter range limits (cont. below with Ranges 3-5)
Range 2 span Range 3 span Range 4 span Range 5 span
Units min max min max min max min max
inH
2
O 2.5 250 10 1000 83.040 8304 553.60 55360
inHg 0.18389 18.389 0.73559 73.559 6.1081 610.81 40.720 4072.04
ftH
2
O 0.20833 20.8333 0.83333 83.3333 6.9198 691.997 46.13 4613.31
mmH
2
O 63.553 6355 254 25421 2110.95 211095 14073 1407301
mmHg 4.67082 467.082 18.6833 1868.33 155.145 15514.5 1034.3 103430
psi 0.0902 9.03183 0.36127 36.127 3 300 20 2000
bar 0.00623 0.62272 0.02491 2.491 0.20684 20.6843 1.37895 137.895
mbar 6.22723 622.723 24.9089 2490.89 206.843 20684.3 1378.95 137895
g/cm
2
6.33875 633.875 25.355 2535.45 210.547 21054.7 1406.14 140614
kg/cm
2
0.00635 0.635 0.0254 2.54 0.21092 21.0921 1.40614 140.614
Pa 622.723 62160.6 2490.89 249089 20684.3 2068430 137895 13789500
kPa 0.62272 62.2723 2.49089 249.089 20.6843 2068.43 137.895 13789.5
torr 4.67082 467.082 18.6833 1868.33 155.145 15514.5 1034.3 103430
atm 0.00615 0.61460 0.02458 2.458 0.20414 20.4138 1.36092 136.092
When using a Field Communicator, ±5% adjustment is allowed on the sensor limit to allow for unit conversions.
Range 1 span Range 2 span
Units min max min max
inH
2
O 8.30397 831.889 41.5198 4159.45
inHg 0.61081 61.0807 3.05403 305.403
ftH
2
O 0.69199 69.3241 3.45998 345.998
mmH
2
O 211.10 21130 1054.60 105460.3
mmHg 15.5145 1551.45 77.5723 7757.23
psi 0.3 30 1.5 150
bar 0.02068 2.06843 0.10342 10.3421
mbar 20.6843 2068.43 103.421 10342.11
g/cm
2
21.0921 2109.21 105.461 10546.1
kg/cm
2
0.02109 2.10921 0.10546 10.5461
Pa 2068.43 206843 10342.1 1034212
kPa 2.06843 206.843 10.3421 1034.21
torr 15.5145 1551.45 77.5726 7757.26
atm 0.02041 2.04138 0.10207 10.2069
When using a Field Communicator, ±5% adjustment is allowed on the sensor limit to allow for unit conversions.